Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

residual current monitoring relay, Vigirex RMH, 30 mA to 30A, 220/240 VAC 50/60Hz, front panel mounting

Schneider
SKU
SE_LV481004
Model
LV481004
SGD $664.24
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 4 To 6 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
MAIN
RangeVigiPacT
Device Short NameRMH
Product Or Component TypeMonitoring relay
Relay ApplicationMonitoring relay
Mounting SupportFront panel
Type Of SettingKeypad
Modbus address
Residual Earth-leakage Sensitity Adjustment TypeAdjustable
Earth-leakage Sensitivity0.03…1 A, adjustable in step of 0.001 A
1…30 A, adjustable in step of 0.1 A
Earth-leakage Time DelayInstantaneous for 0.03 A
Adjustable 0…4.5 s for 0.03…30 A adjustable in step of 10 ms
Threshold Setting0.015...1 A adjustable in step of 0.001 A pre-alarm
1...30 A adjustable in step of 0.1 A pre-alarm
0.03...1 A adjustable in step of 0.001 A alarm
1...30 A adjustable in step of 0.1 A alarm
Current Sensors CompatibilityVigiPacT TOA earth leakage current sensor
VigiPacT A earth leakage current sensor
VigiPacT L earth leakage current sensor
VigiPacT RM12T multiplexer
[Ithe] Conventional Enclosed Thermal Current8 A
Minimum Load10 mA at 12 V
[Us] Rated Supply Voltage220...240 V AC 50/60 Hz 70...110 %
Power Consumption In VA8 VA
Monitored Distribution System1000 V - AC at 50/60 Hz (maximum)
1000 V - AC at 400 Hz (maximum)
Earthing SystemTN-S
IT
TT
[Uimp] Rated Impulse Withstand Voltage8 kV
COMPLEMENTARY
Test FunctionLocal
Remote test (via communication)
Signal Contacts Composition1 C/O alarm fail-safe
1 NO pre-alarm fail-safe
Type Of MeasurementEarth fault current internal measurement, range: 20...200 %, accuracy: +/- 20 %
Refresh Time0.5 s
Communication ServiceModbus slave
Tamperproof Of SettingsProtected by access code
Connections - TerminalsAlarm circuit: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12
Alarm circuit: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12
Multiplexer connection: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12
Multiplexer connection: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12
Pre alarm: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12
Pre alarm: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12
Voltage presence: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12
Voltage presence: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12
Power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 22...AWG 12
Power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 22...AWG 12
Wire Stripping LengthAlarm circuit: 6 mm
Multiplexer connection: 6 mm
Pre alarm: 6 mm
Voltage presence: 6 mm
Power supply: 6 mm
Tightening TorqueAlarm circuit: 0.5 N.m
Multiplexer connection: 0.5 N.m
Pre alarm: 0.5 N.m
Voltage presence: 0.5 N.m
Power supply: 0.5 N.m
Width72 mm
Height72 mm
Depth117 mm
Cut-out Dimensions68 x 68 mm
Net Weight0.3 kg
IP Degree Of ProtectionIP40 on front face: conforming to EN/IEC 60529
IP30 on side parts: conforming to EN/IEC 60529
IP20 on connection terminals: conforming to EN/IEC 60529
IK Degree Of ProtectionIK07 conforming to EN 50102
Mechanical RobustnessFire resistance conforming to IEC 60695-2-1
IK protection 2 joules: IK07 conforming to EN 50102
Vibrations 13.2...100 Hz: 0.7 g
Vibrations 2...13.2 Hz: +/- 1 mm
ENVIRONMENT
Environmental CharacteristicExposure to damp heat not in service conforming to IEC 60068-2-30
Exposure to damp heat in service conforming to IEC 60068-2-56
Salt mist conforming to IEC 60068-2-52
Overvoltage CategoryIV
Electrical Shock Protection ClassClass II
Electromagnetic CompatibilityConducted and radiated emissions: , B, conforming to CISPR 11
Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6
Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2
High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5
Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4
Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative Humidity95 % at 55 °C
Pollution Degree3 conforming to IEC 60664-1
Ambient Air Temperature For Operation-25…55 °C
Ambient Air Temperature For Storage-40…85 °C
Write Your Own Review
You're reviewing:residual current monitoring relay, Vigirex RMH, 30 mA to 30A, 220/240 VAC 50/60Hz, front panel mounting
Your Rating