Advanced Control Unit, TeSys U, 0.35-1.05A, 3P Motors, Protection & Diagnostic, Class 20, Coil 24V DC.
Schneider
SKU
SE_LUCDT1BL
Model
LUCDT1BL
Obsolete
Short description of LUCDT1BL
Controllers Tesys U up to 450 kW
Obsolete
range : TeSys
-  range of product : TeSys U
-  device short name : LUCD
-  product or component type : Advanced control unit
-  device application : Motor controlMotor protection
-  product specific application : Basic protection and advanced functions, communication
-  main function available : Protection against phase failure and phase imbalanceManual resetProtection against overload and short-circuitEarth fault protection
-  product compatibility : Power base LUTM
-  network frequency : 40...60 Hz
-  load type : 3-phase motor
-  cooling :  self-cooled
-  utilisation category : AC
- 41AC
- 44AC
- 43
-  rated motor current adjustment range : 0.35…1.05 A
-  thermal overload class : Class 20
-  frequency limit :  40…60 Hz
-  temperature compensation- 25…70 °C conforming to IEC 60947-6-2Class 20
-  frequency limit :  40…60 Hz
-  temperature compensation- 25…70 °C conforming to UL 508
-  tripping threshold : 14.2 x Ir +/- 20 %
-  phase failure sensitivity : Yes
-  [Uc] control circuit voltage : 24 V DC
-  range of product : TeSys U
-  device short name : LUCD
-  product or component type : Advanced control unit
-  device application : Motor controlMotor protection
-  product specific application : Basic protection and advanced functions, communication
-  main function available : Protection against phase failure and phase imbalanceManual resetProtection against overload and short-circuitEarth fault protection
-  product compatibility : Power base LUTM
-  network frequency : 40...60 Hz
-  load type : 3-phase motor
-  cooling :  self-cooled
-  utilisation category : AC
- 41AC
- 44AC
- 43
-  rated motor current adjustment range : 0.35…1.05 A
-  thermal overload class : Class 20
-  frequency limit :  40…60 Hz
-  temperature compensation- 25…70 °C conforming to IEC 60947-6-2Class 20
-  frequency limit :  40…60 Hz
-  temperature compensation- 25…70 °C conforming to UL 508
-  tripping threshold : 14.2 x Ir +/- 20 %
-  phase failure sensitivity : Yes
-  [Uc] control circuit voltage : 24 V DC
MAIN SPECIFICATIONS | |
---|---|
Product Or Component Type | advanced control unit |
Range Of Product | TeSys U |
[Uc] Control Circuit Voltage | 24 V DC |
Device Short Name | LUCD |
Function Available | earth fault protection manual reset protection against overload and short-circuit protection against phase failure and phase imbalance |
Product Specific Application | basic protection and advanced functions, communication |
Range | TeSys |
Range Name | TeSys LUTM |
Thermal Overload Class | class 20 - frequency limit: 40-60 Hz - temperature compensation: -25-70 °C conforming to IEC 60947-6-2 class 20 - frequency limit: 40-60 Hz - temperature compensation: -25-70 °C conforming to UL 508 |
Utilisation Category | AC-41 AC-43 AC-44 |
COMPLEMENTARY | |
Compatibility Code | LUCD |
Control Circuit Voltage Limits | 14.5 V for DC circuit 24 V drop-out 20...28 V for DC circuit 24 V in operation |
Depth | 60 mm |
Device Application | motor control motor protection |
Fixing Mode | plug-in (front face) |
Height | 66 mm |
Immunity To Microbreaks | 3 ms |
Load Type | 3-phase motor - cooling: self-cooled |
Network Frequency | 40...60 Hz |
Operating Time | 35 ms opening for control circuit 70 ms closing for control circuit |
Phase Failure Sensitivity | yes |
Product Compatibility | power base LUTM |
Reset | manual reset |
Thermal Protection Adjustment Range | 0.35-1.05 A |
Tripping Threshold | 14.2 x Ir +/- 20 % |
Typical Current Consumption | 130 mA at 24 V DC I maximum while closing 60 mA at 24 V DC I rms sealed |
Width | 45 mm |
[Uimp] Rated Impulse Withstand Voltage | 4 kV conforming to IEC 60947-6-2 |
[Ui] Rated Insulation Voltage | 250 V conforming to CSA C22.2 No 60947-4-1 250 V conforming to IEC 60947-6-2 250 V conforming to UL 60947-4-1 |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-70 °C |
Ambient Air Temperature For Storage | -40-85 °C |
Fire Resistance | 650 °C conforming to IEC 60695-2-12 960 °C parts supporting live components conforming to IEC 60695-2-12 |
Heat Dissipation | 2-2 W for control circuit |
Immunity To Radioelectric Fields | 10 V conforming to IEC 61000-4-6 |
Immunity To Voltage Dips | 70 % / 500 ms conforming to IEC 61000-4-11 |
IP Degree Of Protection | IP20 front panel and wired terminals conforming to IEC 60947-1 IP20 other faces conforming to IEC 60947-1 IP40 front panel outside connection zone conforming to IEC 60947-1 |
Non-dissipating Shock Wave | 1 kV serial mode conforming to IEC 60947-6-2 2 kV common mode conforming to IEC 60947-6-2 |
Operating Altitude | 2000 m |
Product Certifications | CSA UL |
Protective Treatment | TH conforming to IEC 60068 |
Resistance To Electrostatic Discharge | 8 kV level 3 in open air conforming to IEC 61000-4-2 8 kV level 4 on contact conforming to IEC 61000-4-2 |
Resistance To Fast Transients | 2 kV class 3 serial link conforming to IEC 61000-4-4 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
Resistance To Radiated Fields | 10 V/m 3 conforming to IEC 61000-4-3 |
Shock Resistance | 10 gn power poles open conforming to IEC 60068-2-27 15 gn power poles closed conforming to IEC 60068-2-27 |
Standards | CSA C22.2 No 14 EN 60947-6-2 IEC 60947-6-2 UL 508 |
Vibration Resistance | 2 gn, 5-300 Hz, power poles open conforming to IEC 60068-2-6 4 gn, 5-300 Hz, power poles closed conforming to IEC 60068-2-6 |
OTHER | |
Poles Description | advanced control unit |
[Us] Rated Supply Voltage | TeSys U |