Advanced control unit, TeSys U, 9.5-38A, 3P motors, protection & diagnostic, class 20, coil 110-240V AC/DC

Schneider
SKU
SE_LUCD38FU
Model
LUCD38FU
SGD $198.81

Short description of LUCD38FU

TeSys U control and diagnostic unit to be inserted in advanced power bases LUB380 to form a TeSys U starter controller, for 3-phase motor applications up to 18.5kW@400V. It provides full protection to motors with a rated current Ir 9.5-38A (Ir adjustable), overload tripping class 20, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). It provides a thermal overload alarm to be used locally using a LUFDA module or remotely using a LULC module, and a test push button for overload simulation. To be used with a 110-240V AC / 110-220V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base). Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 14 To 16 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
MAIN
RangeTeSys
Range Of ProductTeSys Ultra
Product NameTeSys Ultra
Device Short NameLUCD
Product Or Component TypeAdvanced control unit
Device ApplicationMotor control
Motor protection
Product Specific ApplicationBasic protection and advanced functions, communication
Main Function AvailableProtection against phase failure and phase imbalance
Protection against overload and short-circuit
Earth fault protection
Manual reset
Product CompatibilityPower base LUB38
Power base LUB380
Reversing contactor breaker LU2B38FU
[Ue] Rated Operational Voltage690 V AC
Network Frequency40...60 Hz
Load Type3-phase motor - cooling: self-cooled
Utilisation CategoryAC-43
Motor Power KW18.5 kW at 400...440 V AC 50/60 Hz
18.5 kW at 500 V AC 50/60 Hz
22 kW at 690 V AC 50/60 Hz
Rated Motor Current Adjustment Range9.5…38 A
Thermal Overload ClassClass 20 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to IEC 60947-6-2
Class 20 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to UL 508
Tripping Threshold14.2 x Ir +/- 20 %
Phase Failure SensitivityYes
[Uc] Control Circuit Voltage110...240 V AC
110...220 V DC
COMPLEMENTARY
Control Circuit Voltage Limits88...264 V for AC circuit 110...240 V in operation
88...242 V for DC circuit 110...220 V in operation
55 V for AC circuit 110...240 V drop-out
55 V for DC circuit 110...220 V drop-out
Typical Current Consumption280 mA at 110...240 V AC I maximum while closing with LUB32
280 mA at 110...240 V AC I maximum while closing with LUB38
280 mA at 110...220 V DC I maximum while closing with LUB32
280 mA at 110...220 V DC I maximum while closing with LUB38
25 mA at 110...240 V AC I rms sealed with LUB32
25 mA at 110...240 V AC I rms sealed with LUB38
25 mA at 110...220 V DC I rms sealed with LUB32
25 mA at 110...220 V DC I rms sealed with LUB38
Heat Dissipation3 W for control circuit with LUB38
Operating Time35 ms opening with LUB38 for control circuit
50 ms closing with LUB38 for control circuit
ResetManual reset
StandardsEN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
Product CertificationsCE
UL
CSA
CCC (pending)
EAC (pending)
[Ui] Rated Insulation Voltage690 V conforming to IEC 60947-6-2
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947-6-2
Safe Separation Of Circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing ModePlug-in (front face)
Width45 mm
Height66 mm
Depth60 mm
Net Weight0.135 kg
Compatibility CodeLUCD
ENVIRONMENT
IP Degree Of ProtectionIP20 front panel and wired terminals conforming to IEC 60947-1
IP20 other faces conforming to IEC 60947-1
IP40 front panel outside connection zone conforming to IEC 60947-1
Protective TreatmentTH conforming to IEC 60068
Ambient Air Temperature For Operation-25…70 °C
Ambient Air Temperature For Storage-40…85 °C
Operating Altitude2000 m
Fire Resistance960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
Shock Resistance10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Vibration Resistance2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6
4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance To Electrostatic Discharge8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
Non-dissipating Shock Wave1 kV serial mode conforming to IEC 60947-6-2
2 kV common mode conforming to IEC 60947-6-2
Resistance To Radiated Fields10 V/m 3 conforming to IEC 61000-4-3
Resistance To Fast Transients2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity To Radioelectric Fields10 V conforming to IEC 61000-4-6
Immunity To Microbreaks3 ms
Immunity To Voltage Dips70 % / 500 ms conforming to IEC 61000-4-11
Write Your Own Review
You're reviewing:Advanced control unit, TeSys U, 9.5-38A, 3P motors, protection & diagnostic, class 20, coil 110-240V AC/DC
Your Rating