Advanced power base, TeSys U, 3P, 38A/690V

Schneider
SKU
SE_LUB380
Model
LUB380
SGD $181.98

Short description of LUB380

TeSys U advanced power base, 3 poles (3NO), 38A/690V, to be completed with a control unit LUC to form a TeSys U starter controller, for 3-phase motor applications up to 18.5kW@400V. Base composed of power contacts, control coil, rotary handle, with a modular design for additional modules to form a "all in one" starter controller with basic or advanced protection and control functions. It is equipped with auxiliary signaling contacts (1NO+1NC), a control terminal block, and blanking shutters covering the empty cavities. It provides a high breaking capacity Icu 25kA@400V, start-stop control guaranteed for 3600 cycles/hour. Very compact (45mm width), DIN-rail mounting and screw fixing, with a padlockable rotary handle. Certified when used in conjunction with a LUC control unit (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 14 To 16 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
MAIN
RangeTeSys
Product NameTeSys Ultra
Device Short NameLUB
Product Or Component TypeNon reversing power base
Device ApplicationMotor control
Motor protection
Poles Description3P
Suitability For IsolationYes
[Ue] Rated Operational Voltage690 V AC for power circuit
Network Frequency40...60 Hz
[Ith] Conventional Free Air Thermal Current38 A
[Ie] Rated Operational Current35 A at <= 440 V
28 A at 500 V
24 A at 690 V
Utilisation CategoryAC-43
AC-41
[Ics] Rated Service Breaking Capacity25 kA at 230 V
25 kA at 440 V
10 kA at 500 V
4 kA at 690 V
Auxiliary Contact Composition1 NO + 1 NC
Auxiliary Contacts Typetype linked contacts (1 NO + 1 NC) conforming to IEC 60947-4-1
type mirror contact (1 NC) conforming to IEC 60947-1
[Uc] Control Circuit Voltage24 V AC 50/60 Hz
24 V DC
48...72 V AC 50/60 Hz
48...72 V DC
110...240 V AC 50/60 Hz
110...220 V DC
COMPLEMENTARY
Typical Current Consumption200 mA at 24 V DC I maximum while closing with LUCM
220 mA at 24 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
220 mA at 24 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
25 mA at 110...220 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
25 mA at 110...240 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
280 mA at 110...220 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 110...240 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V AC I maximum while closing with LUCA, LUCB, LUCC, LUCD
280 mA at 48...72 V DC I maximum while closing with LUCA, LUCB, LUCC, LUCD
45 mA at 48...72 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
45 mA at 48...72 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
75 mA at 24 V DC I rms sealed with LUCM
80 mA at 24 V DC I rms sealed with LUCA, LUCB, LUCC, LUCD
90 mA at 24 V AC I rms sealed with LUCA, LUCB, LUCC, LUCD
Heat Dissipation3 W for control circuit with LUCA, LUCB, LUCC, LUCD
1.8 W for control circuit with LUCM
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Operating Time35 ms opening with LUCA, LUCB, LUCC, LUCD, LUCM for control circuit
50 ms at >= 72 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
60 ms at 48 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
70 ms at 24 V closing with LUCA, LUCB, LUCC, LUCD for control circuit
65 ms closing with LUCM for control circuit
Mechanical Durability15 Mcycles
Maximum Operating Rate3600 cyc/h
Product CertificationsCE
UL
CSA
CCC
EAC
StandardsEN 60947-6-2
IEC 60947-6-2
UL 60947-4-1, with phase barrier
CSA C22.2 No 60947-4-1, with phase barrier
[Ui] Rated Insulation Voltage690 V conforming to IEC 60947-6-2 (pollution degree 3)
600 V conforming to UL 60947-4-1
600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947-6-2
Safe Separation Of Circuit400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1 appendix N
400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1 appendix N
Fixing ModeClipped (DIN rail)
Screw-fixed (plate)
Connections - TerminalsPower circuit: screw clamp terminals 1 cable(s) 1…10 mm² rigid
Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² flexible without cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² flexible with cable end
Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² rigid
Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² flexible without cable end
Control circuit: without connection
Tightening TorqueControl circuit: 0.8…1.2 N.m flat screwdriver 5 mm
Control circuit: 0.8…1.2 N.m Philips no 1 screwdriver 5 mm
Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm
Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm
Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm
Width45 mm
Height154 mm
Depth126 mm
Net Weight0.865 kg
Compatibility CodeLUB
ENVIRONMENT
IP Degree Of ProtectionIP20 conforming to IEC 60947-1 (front panel and wired terminals)
IP20 conforming to IEC 60947-1 (other faces)
IP40 conforming to IEC 60947-1 (front panel outside connection zone)
Protective TreatmentTH conforming to IEC 60068
Ambient Air Temperature For Operation-25…60 °C with LUCM
-25…70 °C with LUCA, LUCB, LUCC, LUCD
Ambient Air Temperature For Storage-40…85 °C
Fire Resistance960 °C parts supporting live components conforming to IEC 60695-2-12
650 °C conforming to IEC 60695-2-12
Operating Altitude2000 m
Shock Resistance10 gn power poles open conforming to IEC 60068-2-27
15 gn power poles closed conforming to IEC 60068-2-27
Vibration Resistance2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27
4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27
Resistance To Electrostatic Discharge8 kV level 3 in open air conforming to IEC 61000-4-2
8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance To Radiated Fields10 V/m 3 conforming to IEC 61000-4-3
Resistance To Fast Transients2 kV class 3 serial link conforming to IEC 61000-4-4
4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Non-dissipating Shock Wave1 kV serial mode 24...240 V AC conforming to IEC 60947-6-2
1 kV serial mode 48...220 V DC conforming to IEC 60947-6-2
2 kV common mode 24...240 V AC conforming to IEC 60947-6-2
2 kV common mode 48...220 V DC conforming to IEC 60947-6-2
Immunity To Radioelectric Fields10 V conforming to IEC 61000-4-6
Immunity To Microbreaks3 ms for control circuit
Immunity To Voltage Dips70 % / 500 ms conforming to IEC 61000-4-11