Motor Management, TeSys T, Motor Controller, CANopen, 6 Logic Inputs, 3 Relay Logic Outputs, 5 To 100A, 100 To 240 VAC
Schneider
SKU
SE_LTMR100CFM
Model
LTMR100CFM
SGD $1,427.51
Short description of LTMR100CFM
CONTROLLER CANOPEN 5 100A 115 230VAC
Country of Origin
China
motor controller LTMR TeSys T
-  100..240 V AC 100 A for CANopen.
Label :  Tesys T
-  range :  TeSys
-  communication port protocol :  CANopen
-  bus type :  CANopen ISO 1198 1...127, transmission rate :  10...1000 kbit/s, SUB
- D 9 with 4 twisted shielded pairs cable, CANopen ISO 1198 1...127, transmission rate :  10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable
-  product name :  TeSys T
-  device short name :  LTMR
-  product or component type :  motor controller
-  device application :  equipment monitoring and control
-  measurement current :  5-100 A
-  [Us] rated supply voltage :  100...240 V AC 50/60 Hz
-  current consumption :  8...62.8 mA
-  supply voltage limits :  93.5-264 V AC
-  Range Presentation :  TeSys T is an advanced motor management and protection system designed to prevent malfunctions. Both motor and mechanics are protected, so unexpected process or production halts can be anticipated.
TeSys T comprises : 
-  A controller providing main protection and control functions
-  An extension module that completes the functions of the controller by providing voltage and power protection and monitoring
-  An LTMCU operator control unit for reading, diagnostics and modification of the parameters monitored SoMove configuration software, enables simple and user-friendly setup of motor starters incorporated with TeSys T.
Fully open, it communicates with commonly used Ethernet networks and protocols :  Modbus/TCP and EtherNet/IP, and can also communicate via Modbus, CANopen, DeviceNet, PROFIBUS DP protocols.
-  Range Benefits :  Give your motor starters a sixth sense!
-  TeSys T incorporates a communication interface for remote supervision and control of the motor.
-  Open to all communication protocols, TeSys T can efficiently replace all existing relays.
-  Range Application Presentation :  Industrial installations such as : 
-  Oil & gas
-  Mining and mineral
-  Water treatment
-  Metallurgy
-  Pulp & paper
-  Pharmaceutical Integration in intelligent Motor Control centre applications for : 
-  Pumping, ventilation, filtering
-  Compressors, mixers, crushers, conveyor systems
-  100..240 V AC 100 A for CANopen.
Label :  Tesys T
-  range :  TeSys
-  communication port protocol :  CANopen
-  bus type :  CANopen ISO 1198 1...127, transmission rate :  10...1000 kbit/s, SUB
- D 9 with 4 twisted shielded pairs cable, CANopen ISO 1198 1...127, transmission rate :  10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable
-  product name :  TeSys T
-  device short name :  LTMR
-  product or component type :  motor controller
-  device application :  equipment monitoring and control
-  measurement current :  5-100 A
-  [Us] rated supply voltage :  100...240 V AC 50/60 Hz
-  current consumption :  8...62.8 mA
-  supply voltage limits :  93.5-264 V AC
-  Range Presentation :  TeSys T is an advanced motor management and protection system designed to prevent malfunctions. Both motor and mechanics are protected, so unexpected process or production halts can be anticipated.
TeSys T comprises : 
-  A controller providing main protection and control functions
-  An extension module that completes the functions of the controller by providing voltage and power protection and monitoring
-  An LTMCU operator control unit for reading, diagnostics and modification of the parameters monitored SoMove configuration software, enables simple and user-friendly setup of motor starters incorporated with TeSys T.
Fully open, it communicates with commonly used Ethernet networks and protocols :  Modbus/TCP and EtherNet/IP, and can also communicate via Modbus, CANopen, DeviceNet, PROFIBUS DP protocols.
-  Range Benefits :  Give your motor starters a sixth sense!
-  TeSys T incorporates a communication interface for remote supervision and control of the motor.
-  Open to all communication protocols, TeSys T can efficiently replace all existing relays.
-  Range Application Presentation :  Industrial installations such as : 
-  Oil & gas
-  Mining and mineral
-  Water treatment
-  Metallurgy
-  Pulp & paper
-  Pharmaceutical Integration in intelligent Motor Control centre applications for : 
-  Pumping, ventilation, filtering
-  Compressors, mixers, crushers, conveyor systems
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 100...240 V AC 50/60 Hz |
Contacts Type And Composition | 1 NO + 1 NC fault signal 3 NO |
Discrete Input Number | 1 NO + 1 NC fault signal 3 NO |
Measurement Accuracy | +/- 30 min/year internal clock 0,02 current 0,02 temperature 1 % voltage (100...830 V) 3 % power factor 5 % active and reactive power 5 % earth fault current external measurement 5...15 % earth fault current internal measurement |
Product Or Component Type | motor controller |
Communication Port Protocol | CANopen |
Device Short Name | LTMR |
EAN13 | 3389119404730 |
Range | TeSys |
Range Name | TeSys T |
COMPLEMENTARY | |
Product Name | TeSys T |
Time Delay | +/- 30 min/year internal clock 0,02 current 0,02 temperature 1 % voltage (100...830 V) 3 % power factor 5 % active and reactive power 5 % earth fault current external measurement 5...15 % earth fault current internal measurement |
Associated Fuse Rating | 0.5 A gG for control circuit 4 A gG for output |
Bus Type | CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, SUB-D 9 with 4 twisted shielded pairs cable CANopen ISO 1198 interface, addressing 1...127, transmission rate 10...1000 kbit/s, terminal block with 4 twisted shielded pairs cable |
Compatibility Code | LTMR |
Connection Pitch | 5.08 mm |
Connections - Terminals | control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 1 cable(s) 0.2-2.5 mm² (AWG 24...AWG 14) solid without cable end control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 1 cable(s) 0.25-2.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) flexible with cable end control circuit: connector 2 cable(s) 0.2-1 mm² (AWG 24...AWG 14) solid without cable end control circuit: connector 2 cable(s) 0.2-1.5 mm² (AWG 24...AWG 14) flexible without cable end control circuit: connector 2 cable(s) 0.5-1.5 mm² (AWG 24...AWG 14) flexible without cable end |
Current Consumption | 8...62.8 mA |
Current State 0 Guaranteed | logic input: 0...40 V and <= 15 mA for 25 ms |
Current State 1 Guaranteed | logic input: 79...264 V and >= 2 mA for 25 ms |
Depth | 122.5 mm |
Device Application | equipment monitoring and control |
Height | 61 mm |
Input Current | 3.1 mA at 100 V 7.5 mA at 240 V |
Load Current | 5 A at 250 V AC for logic output 5 A at 30 V DC for logic output |
Logic Input Number | 6 |
Maximum Operating Frequency | 2 Hz |
Maximum Operating Rate | 1800 cyc/h |
Measurement Current | 5-100 A |
Mechanical Robustness | shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27 vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 |
Metering Type | average current Iavg earth-fault current imbalance current phase current I1, I2, I3 RMS temperature |
Net Weight | 0.53 kg |
Network And Machine Diagnosis Type | event recording fault recording motor control command recording phase fault and earth fault trip counters remaining operating time before overload tripping running hours counter/operating time starting current and time trip context information trip history information waiting time after overload tripping |
Permissible Power | 30 W (DC-13), Ie = 1.25 A, 500000 cycles (output) 480 VA (AC-15), Ie = 2 A, 500000 cycles (output) |
Protection Type | earth-leakage protection load fluctuation locked rotor overload overload (long time) phase failure phase unbalance power factor variation reverse polarity protection thermal overload protection thermal protection |
Short-circuit Withstand | 100 kA conforming to EN/IEC 60947-4-1 |
Supply Voltage Limits | 93.5-264 V AC |
Tightening Torque | control circuit: 0.5-0.6 N.m flat screwdriver 3 mm |
Web Services | web server |
Width | 91 mm |
[Uimp] Rated Impulse Withstand Voltage | 0.8 kV communication circuit conforming to EN/IEC 60947-4-1 4 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 |
[Ui] Rated Insulation Voltage | 690 V conforming to CSA C22.2 No 14 690 V conforming to EN/IEC 60947-1 690 V conforming to UL 508 |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -20-60 °C |
Ambient Air Temperature For Storage | -40-80 °C |
Electromagnetic Compatibility | communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 control circuit: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 |
Fire Resistance | 650 °C conforming to EN/IEC 60695-2-12 960 °C conforming to UL 94 |
IP Degree Of Protection | IP20 |
Operating Altitude | <= 2000 m without derating |
Overvoltage Category | III |
Pollution Degree | 3 |
Product Certifications | ABS ATEX BV CCC CSA C-Tick DNV EAC GL KERI LROS (Lloyds register of shipping) NOM RINA RMRoS UL |
Protective Treatment | 12 x 24 hour cycles conforming to EN/IEC 60068-2-30 48 h conforming to EN/IEC 60070-2-11 TH conforming to EN/IEC 60068 |
Standards | CSA C22.2 No 14 EN 60947-4-1 IACS E10 IEC 60947-4-1 UL 508 |
OTHER | |
Poles Description | motor controller |
[Us] Rated Supply Voltage | 100...240 V AC 50/60 Hz |
Write Your Own Review