contactor TeSys LC1-D - 3 poles - AC-3 440V 9 A - coil 24 V AC
Schneider
SKU
SE_LC1D09B7TQ
Model
LC1D09B7TQ
SGD $27.82
Short description of LC1D09B7TQ
TeSys D contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Country of Origin
France
MAIN | |
---|---|
Range | TeSys TeSys Deca |
Range Of Product | TeSys Deca |
Product Or Component Type | Contactor |
Device Short Name | LC1D |
Contactor Application | Motor control Resistive load |
Utilisation Category | AC-3 AC-1 AC-3e |
Poles Description | 3P |
[Ue] Rated Operational Voltage | Power circuit: <= 690 V AC 25...400 Hz |
[Ie] Rated Operational Current | 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
[Uc] Control Circuit Voltage | 24 V AC 50/60 Hz |
COMPLEMENTARY | |
Motor Power KW | 4 kW at 380...400 V AC 50/60 Hz 5.5 kW at 500 V AC 50/60 Hz 5.5 kW at 660...690 V AC 50/60 Hz 4 kW at 415...440 V AC 50/60 Hz 2.2 kW at 220...230 V AC 50/60 Hz 2.2 kW at 400 V AC (AC-4) |
Motor Power Hp | 0.5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA 0.5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL 1 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA 1 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to CSA 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors conforming to CSA 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors conforming to UL 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to CSA 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to UL 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to CSA 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to UL 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to UL |
Compatibility Code | LC1D |
Pole Contact Composition | 3 NO |
Protective Cover | With |
[Ith] Conventional Free Air Thermal Current | 10 A (at 60 °C) for control circuit 25 A (at 60 °C) for power circuit |
Irms Rated Making Capacity | 140 A AC for control circuit conforming to IEC 60947-5-1 250 A at 440 V for power circuit conforming to IEC 60947 |
Rated Breaking Capacity | 250 kA at 440 V for power circuit conforming to IEC 60947 |
Associated Fuse Rating | 10 A gG for control circuit conforming to IEC 60947-5-1 20 A at <= 690 V coordination type 2 for power circuit 25 A at <= 690 V coordination type 1 for power circuit |
Average Impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
Power Dissipation Per Pole | 0.2 W AC-3 1.56 W AC-1 0.2 W AC-3e |
[Ui] Rated Insulation Voltage | Control circuit: 600 V CSA certified Control circuit: 600 V UL certified Power circuit: 600 V CSA certified Power circuit: 600 V UL certified Control circuit: 690 V conforming to IEC 60947-4-1 Power circuit: 690 V conforming to IEC 60947-4-1 |
Overvoltage Category | III |
[Uimp] Rated Impulse Withstand Voltage | 6 kV conforming to IEC 60947 |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
Mechanical Durability | 15000000 cycles |
Control Circuit Type | AC at 50/60 Hz |
Coil Technology | Without built-in bidirectional peak limiting diode suppressor |
Control Circuit Voltage Limits | 0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz 0.8...1.1 Uc (60 °C):operational AC 50 Hz 0.85...1.1 Uc (60 °C):operational AC 60 Hz |
Inrush Power In VA | 70 VA cos phi 0.75 (at 20 °C) |
Hold-in Power Consumption In VA | 7 VA 50/60 Hz cos phi 0.3 (at 20 °C) |
Heat Dissipation | 2…3 W at 50/60 Hz for control circuit |
Operating Time | 4...19 ms opening 12...22 ms closing |
Maximum Operating Rate | 3600 cyc/h 60 °C |
Connections - Terminals | Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminal 2 1…2.5 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable end Power circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable end Power circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible with cable end Power circuit: screw clamp terminal 2 1…2.5 mm² - cable stiffness: flexible with cable end |
Tightening Torque | Control circuit: 1.7 N.m - with screwdriver flat Ø 6 mm Control circuit: 1.7 N.m - with screwdriver Philips No 2 Power circuit: 1.7 N.m - with screwdriver flat Ø 6 mm Power circuit: 1.7 N.m - with screwdriver Philips No 2 Control circuit: 1.7 N.m - with screwdriver pozidriv No 2 Power circuit: 1.7 N.m - with screwdriver pozidriv No 2 |
Auxiliary Contact Composition | 1 NO + 1 NC |
Minimum Switching Voltage | 17 V for control circuit |
Minimum Switching Current | 5 mA for control circuit |
Insulation Resistance | > 10 MOhm for control circuit |
Non-overlap Time | 1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts |
Mounting Support | Plate Rail |
ENVIRONMENT | |
Standards | EN/IEC 60947-4-1 UL 508 CSA C22.2 No 14 EN/IEC 60947-5-1 IEC 60335-1 |
Product Certifications | UL DNV BV CSA LROS (Lloyds register of shipping) CCC GOST GL RINA UKCA |
IP Degree Of Protection | IP2X conforming to IEC 60529 IP2X conforming to VDE 0106 |
Climatic Withstand | conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
Permissible Ambient Air Temperature Around The Device | -5…60 °C -40…70 °C at Uc |
Operating Altitude | 3000 m without derating |
Fire Resistance | 850 °C conforming to IEC 60695-2-1 |
Flame Retardance | V1 conforming to UL 94 |
Mechanical Robustness | Shocks contactor opened (10 Gn for 11 ms) Shocks contactor closed (15 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) |
Height | 77 mm |
Width | 45 mm |
Depth | 86 mm |
Net Weight | 3.2 kg |
Quantity Per Set | Set of 10 |
Write Your Own Review