Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

contactor TeSys LC1-D - 3 poles - AC-3 440V 9 A - coil 24 V AC

Schneider
SKU
SE_LC1D09B7TQ
Model
LC1D09B7TQ
SGD $27.82

Short description of LC1D09B7TQ

TeSys D contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 0

Minimum Order Quantity: 24

Backorder Leadtime: 13 To 15 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
MAIN
RangeTeSys
TeSys Deca
Range Of ProductTeSys Deca
Product Or Component TypeContactor
Device Short NameLC1D
Contactor ApplicationMotor control
Resistive load
Utilisation CategoryAC-3
AC-1
AC-3e
Poles Description3P
[Ue] Rated Operational VoltagePower circuit: <= 690 V AC 25...400 Hz
[Ie] Rated Operational Current9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] Control Circuit Voltage24 V AC 50/60 Hz
COMPLEMENTARY
Motor Power KW4 kW at 380...400 V AC 50/60 Hz
5.5 kW at 500 V AC 50/60 Hz
5.5 kW at 660...690 V AC 50/60 Hz
4 kW at 415...440 V AC 50/60 Hz
2.2 kW at 220...230 V AC 50/60 Hz
2.2 kW at 400 V AC (AC-4)
Motor Power Hp0.5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA
0.5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL
1 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA
1 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL
2 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to CSA
2 hp at 230/240 V AC 50/60 Hz for 3 phases motors conforming to CSA
2 hp at 230/240 V AC 50/60 Hz for 3 phases motors conforming to UL
5 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to CSA
5 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to UL
7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to CSA
7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to UL
2 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to UL
Compatibility CodeLC1D
Pole Contact Composition3 NO
Protective CoverWith
[Ith] Conventional Free Air Thermal Current10 A (at 60 °C) for control circuit
25 A (at 60 °C) for power circuit
Irms Rated Making Capacity140 A AC for control circuit conforming to IEC 60947-5-1
250 A at 440 V for power circuit conforming to IEC 60947
Rated Breaking Capacity250 kA at 440 V for power circuit conforming to IEC 60947
Associated Fuse Rating10 A gG for control circuit conforming to IEC 60947-5-1
20 A at <= 690 V coordination type 2 for power circuit
25 A at <= 690 V coordination type 1 for power circuit
Average Impedance2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power Dissipation Per Pole0.2 W AC-3
1.56 W AC-1
0.2 W AC-3e
[Ui] Rated Insulation VoltageControl circuit: 600 V CSA certified
Control circuit: 600 V UL certified
Power circuit: 600 V CSA certified
Power circuit: 600 V UL certified
Control circuit: 690 V conforming to IEC 60947-4-1
Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage CategoryIII
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947
Safety Reliability LevelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical Durability15000000 cycles
Control Circuit TypeAC at 50/60 Hz
Coil TechnologyWithout built-in bidirectional peak limiting diode suppressor
Control Circuit Voltage Limits0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz
0.8...1.1 Uc (60 °C):operational AC 50 Hz
0.85...1.1 Uc (60 °C):operational AC 60 Hz
Inrush Power In VA70 VA cos phi 0.75 (at 20 °C)
Hold-in Power Consumption In VA7 VA 50/60 Hz cos phi 0.3 (at 20 °C)
Heat Dissipation2…3 W at 50/60 Hz for control circuit
Operating Time4...19 ms opening
12...22 ms closing
Maximum Operating Rate3600 cyc/h 60 °C
Connections - TerminalsControl circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable end
Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible without cable end
Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible with cable end
Control circuit: screw clamp terminal 2 1…2.5 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable end
Power circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable end
Power circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible with cable end
Power circuit: screw clamp terminal 2 1…2.5 mm² - cable stiffness: flexible with cable end
Tightening TorqueControl circuit: 1.7 N.m - with screwdriver flat Ø 6 mm
Control circuit: 1.7 N.m - with screwdriver Philips No 2
Power circuit: 1.7 N.m - with screwdriver flat Ø 6 mm
Power circuit: 1.7 N.m - with screwdriver Philips No 2
Control circuit: 1.7 N.m - with screwdriver pozidriv No 2
Power circuit: 1.7 N.m - with screwdriver pozidriv No 2
Auxiliary Contact Composition1 NO + 1 NC
Minimum Switching Voltage17 V for control circuit
Minimum Switching Current5 mA for control circuit
Insulation Resistance> 10 MOhm for control circuit
Non-overlap Time1.5 ms on de-energisation between NC and NO contacts
1.5 ms on energisation between NC and NO contacts
Mounting SupportPlate
Rail
ENVIRONMENT
StandardsEN/IEC 60947-4-1
UL 508
CSA C22.2 No 14
EN/IEC 60947-5-1
IEC 60335-1
Product CertificationsUL
DNV
BV
CSA
LROS (Lloyds register of shipping)
CCC
GOST
GL
RINA
UKCA
IP Degree Of ProtectionIP2X conforming to IEC 60529
IP2X conforming to VDE 0106
Climatic Withstandconforming to IACS E10 exposure to damp heat
conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible Ambient Air Temperature Around The Device-5…60 °C
-40…70 °C at Uc
Operating Altitude3000 m without derating
Fire Resistance850 °C conforming to IEC 60695-2-1
Flame RetardanceV1 conforming to UL 94
Mechanical RobustnessShocks contactor opened (10 Gn for 11 ms)
Shocks contactor closed (15 Gn for 11 ms)
Vibrations contactor opened (2 Gn, 5...300 Hz)
Vibrations contactor closed (4 Gn, 5...300 Hz)
Height77 mm
Width45 mm
Depth86 mm
Net Weight3.2 kg
Quantity Per SetSet of 10
Write Your Own Review
You're reviewing:contactor TeSys LC1-D - 3 poles - AC-3 440V 9 A - coil 24 V AC
Your Rating