Motor Circuit Breaker, TeSys GV2, 3P, 9-14 A, Thermal Magnetic, Spring Terminals.

Schneider
SKU
SE_GV2ME163
Model
GV2ME163
SGD $109.12

Short description of GV2ME163

Circuit-breakers, coordinated with TeSys D contactors, to protect motors up to 32 A (15 kW / 400 V)
Country of Origin
France
-
+

UOM: Piece

In stock
In Stock 0
Backorder Leadtime: 4 To 6 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
range : TeSys
-  product name : TeSys GV2
-  product or component type : Circuit breaker
-  device short name : GV2ME
-  device application : Motor
-  trip unit technology : Thermal
- magnetic
MAIN SPECIFICATIONS
Breaking Capacity100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Contacts Type And Composition14 A
Control Typepush-button
Product Or Component Typecircuit breaker
Range Of ProductTeSys GV2
[Ie] Rated Operational Currentpush-button
[Ue] Rated Operational Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Device Short NameGV2ME
Network TypeAC
Power Dissipation Per Pole2.5 W
RangeTeSys
TeSys Deca
Range NameTeSys GV2
Suitability For Isolationyes conforming to IEC 60947-1
Trip Unit Technologythermal-magnetic
Utilisation CategoryAC-3 conforming to IEC 60947-4-1
category A conforming to IEC 60947-2
[Ics] Rated Service Short-circuit Breaking Capacity100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
50 % at 440 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 500 V AC 50/60 Hz conforming to IEC 60947-2
75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
COMPLEMENTARY
Communication Network Type690 V AC 50/60 Hz conforming to IEC 60947-2
Interlocked Device100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Product NameTeSys Deca
TeSys GV2
[In] Rated Current14 A
Colourdark grey
Compatibility CodeGV2ME
Depth78.5 mm
Device Applicationmotor
Direct Connectorwithout
Electrical Durability100000 cycles for AC-3 at 440 V
Fixing Mode35 mm symmetrical DIN rail: clipped
panel: screwed (with adaptor plate)
Height101 mm
Magnetic Tripping Current170-170 A
Maximum Operating Rate25 cyc/h
Mechanical Durability100000 cycles
Motor Power KW5.5-5.5 kW at 400/415 V AC 50/60 Hz
7.5-7.5 kW at 500 V AC 50/60 Hz
Net Weight0.28 kg
Network Frequency50/60 Hz conforming to IEC 60947-4-1
Operating Positionany position
Phase Failure Sensitivityyes conforming to IEC 60947-4-1
Rated Dutycontinuous conforming to IEC 60947-4-1
Trip Unit Rating9-14 A
Width45 mm
[Ith] Conventional Free Air Thermal Current14 A conforming to IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage6 kV conforming to IEC 60947-2
[Ui] Rated Insulation Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
ENVIRONMENT
Ambient Air Temperature For Operation-20-60 °C
Ambient Air Temperature For Storage-40-80 °C
Fire Resistance960 °C conforming to IEC 60695-2-1
IK Degree Of ProtectionIK04
IP Degree Of ProtectionIP20 conforming to IEC 60529
Operating Altitude2000 m
Product CertificationsATEX
BV
CCC
CSA
DNV-GL
EAC
IECEE CB Scheme
LROS (Lloyds register of shipping)
RINA
UKCA
UL
Protective TreatmentTH
StandardsCSA C22.2 No 60947-4-1
EN/IEC 60947-2
EN/IEC 60947-4-1
UL 60947-4-1
OTHER
Poles Description3P
[Us] Rated Supply VoltageTeSys GV2