Circuit Breaker ComPacT NSX100B, 25kA At 415VAC, MicroLogic 4.2 Vigi Trip Unit 100A, 4 Poles 4d
Schneider
SKU
SE_C10B44V100
Model
C10B44V100
SGD $2,229.03
Short description of C10B44V100
NSX100B 25kA AC 4P4D 100A 4.2
Country of Origin
China
MAIN SPECIFICATIONS | |
---|---|
Breaking Capacity | 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Breaking Capacity Code | B 25 kA 415 V AC |
Contacts Type And Composition | 100 A at 40 °C |
Control Type | toggle |
Product Or Component Type | earth leakage circuit breaker |
Range Of Product | ComPacT NSX100...250 new generation |
Trip Unit Name | Micrologic 4.2 |
[Ie] Rated Operational Current | toggle |
[Ue] Rated Operational Voltage | 440 V AC 50/60 Hz |
Device Short Name | NSX100B |
EAN13 | 3606481993328 |
Earth-leakage Protection Class | class A |
Mounting Support | backplate |
Network Type | AC |
Neutral Position | left |
Protected Poles Description | 3t 3t + N/2 4t |
Range | ComPacT new generation |
Range Name | ComPacT NSX (2021) |
Suitability For Isolation | yes conforming to EN/IEC 60947-2 |
Trip Unit Protection Functions | LSoIR |
Trip Unit Technology | electronic |
Utilisation Category | category A |
COMPLEMENTARY | |
Communication Network Type | 440 V AC 50/60 Hz |
Current Transformer Type | B 25 kA 415 V AC |
Interlocked Device | 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
Product Name | ComPacT NSX new generation |
[Ics] Rated Service Breaking Capacity | 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 |
[In] Rated Current | 100 A at 40 °C |
Compatibility Code | NSX100 |
Connection Pitch | 35 mm |
Depth | 86 mm |
Device Application | distribution |
Downside Connection | front |
Earth-leakage Protection | integrated |
Electrical Durability | 30000 cycles at 440 V In 50000 cycles at 440 V In/2 |
Height | 161 mm |
Instantaneous Pick-up Adjustment Range | 1500 A |
Instantaneous Pick-up Adjustment Type Ii | fixed |
Local Signalling | flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
Long Time Delay Adjustment Type | fixed |
Long Time Pick-up Adjustment Range | 40...100 A |
Long Time Pick-up Adjustment Type Ir | adjustable 9 settings |
Mechanical Durability | 50000 cycles |
Mounting Mode | fixed |
Net Weight | 2.4 kg |
Network Frequency | 50/60 Hz |
Neutral Protection Setting | 0.5 x Ir (3t + N/2) 1 x Ir (4t) no protection (3t) |
Number Of Slots | 5 slot(s) |
Operating Mode | OFF using the IΔn rotary switch |
Power Losses | 5.8 W |
Protection Type | I : for instantaneous short-circuit protection L : for overload protection (long time) R : for earth-leakage protection So : for short time short-circuit protection with fixed delay |
Residual Earth-leakage Sensitity Adjustment Type | adjustable |
Residual Earth-leakage Time Delay Adjustment Type | adjustable |
Short-time Delay Adjustment Type | fixed |
Short-time Pick-up Adjustment Type Isd | adjustable |
Thermal Memory | 20 minutes before and after tripping |
Trip Unit Rating | 100-100 A at 40 °C |
Upside Connection | front |
Width | 140 mm |
Zone Selective Interlocking ZSI | without |
[Isd] Short-time Pick-up Adjustment Range | 1.5...10 x Ir |
[IΔn] Residual Earth-leakage Sensitive Adjustment | 100-100 mA 1-1 A 300-300 mA 30-30 mA 3-3 A 500-500 mA 5-5 A |
[tr] Long-time Delay Adjustment Range | 11-11 s at 7.2 x Ir 16-16 s at 6 x Ir 400-400 s at 1.5 x Ir |
[tsd] Short-time Delay Adjustment Range | 0.02-0.02 s |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
[Ui] Rated Insulation Voltage | 500 V AC 50/60 Hz |
[Δt] Residual Earth-leakage Time Delay Adjustment | 0-0 ms 1-1 s 150-150 ms 500-500 ms 60-60 ms |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-70 °C |
Ambient Air Temperature For Storage | -50-85 °C |
Electrical Shock Protection Class | class II |
IK Degree Of Protection | IK07 conforming to IEC 62262 |
IP Degree Of Protection | IP40 conforming to IEC 60529 |
Operating Altitude | 0...2000 m without derating 2000 m...5000 m with derating |
Overvoltage Category | class II |
Pollution Degree | 3 conforming to IEC 60664-1 |
Product Certifications | CCC EAC Marine |
Relative Humidity | 0-95 % |
Standards | EN/IEC 60947 |
OTHER | |
Earth Leakage Current | Micrologic 4.2 |
Poles Description | 4P |
[Us] Rated Supply Voltage | ComPacT NSX100...250 new generation |
Write Your Own Review