C60 - Circuit Breaker - C60N - 1P - 50A - D Curve.
Schneider
SKU
SE_24578
Model
24578
Obsolete
Short description of 24578
Multi 9 miniature circuit-breakers up to 63A
Obsolete
range of product : C60
-  range : Multi 9
-  product name : C60
-  product or component type : Miniature circuit-breaker
-  device short name : C60N
-  device application : Distribution
-  poles description : 1P
-  number of protected poles : 1
-  [In] rated current : 50 A at 40 °C
-  network type : ACDC
-  trip unit technology : Thermal
- magnetic
-  curve code : D
-  breaking capacity : 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-210 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-23 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-26000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 6089815 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2
-  suitability for isolation : Yes conforming to IEC 60947-2
-  range : Multi 9
-  product name : C60
-  product or component type : Miniature circuit-breaker
-  device short name : C60N
-  device application : Distribution
-  poles description : 1P
-  number of protected poles : 1
-  [In] rated current : 50 A at 40 °C
-  network type : ACDC
-  trip unit technology : Thermal
- magnetic
-  curve code : D
-  breaking capacity : 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-210 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-23 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-26000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 6089815 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2
-  suitability for isolation : Yes conforming to IEC 60947-2
MAIN SPECIFICATIONS | |
---|---|
Breaking Capacity | 10 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 3 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 |
Breaking Capacity Code | N |
Contacts Type And Composition | 50 A at 40 °C |
Control Type | toggle |
Product Or Component Type | miniature circuit-breaker |
Range Of Product | C60 |
[Ie] Rated Operational Current | toggle |
[Ue] Rated Operational Voltage | 130 V AC 50/60 Hz 230...240 V AC 50/60 Hz 230/400 V AC 50/60 Hz 400...415 V AC 50/60 Hz |
Curve Code | D |
Device Short Name | C60N |
Mounting Support | 35 mm symmetrical DIN rail |
Network Type | AC DC |
Number Of Protected Poles | 1 |
Range | Multi 9 |
Range Name | C60 |
Suitability For Isolation | yes conforming to IEC 60947-2 |
Trip Unit Technology | thermal-magnetic |
COMPLEMENTARY | |
Communication Network Type | 130 V AC 50/60 Hz 230...240 V AC 50/60 Hz 230/400 V AC 50/60 Hz 400...415 V AC 50/60 Hz |
Current Transformer Type | N |
Interlocked Device | 10 kA Icu at 230...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 15 kA Icu at 60 V DC 1P conforming to EN/IEC 60947-2 20 kA Icu at 130 V AC 50/60 Hz conforming to EN/IEC 60947-2 3 kA Icu at 400...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6000 A Icn at 230/400 V AC 50/60 Hz conforming to EN 60898 |
Product Name | C60 |
[Ics] Rated Service Breaking Capacity | 15 kA conforming to EN/IEC 60947-2 - 130 V AC 50/60 Hz 2.25 kA conforming to EN/IEC 60947-2 - 400...415 V AC 50/60 Hz 6000 A conforming to EN 60898 - 230/400 V AC 50/60 Hz 7.5 kA conforming to EN/IEC 60947-2 - 230...240 V AC 50/60 Hz |
[In] Rated Current | 50 A at 40 °C |
9 Mm Pitches | 2 |
Comb Busbar And Distribution Block Compatibility | NO |
Compatibility Code | C60 |
Connections - Terminals | tunnel type terminals25-25 mm² flexible tunnel type terminals35-35 mm² rigid |
Contact Position Indicator | yes |
Depth | 73 mm |
Device Application | distribution |
Height | 81 mm |
Limitation Class | 3 conforming to EN/IEC 60947-2 |
Local Signalling | ON/OFF indication |
Magnetic Tripping Limit | 10...14 x In |
Mechanical Durability | 20000 cycles |
Mounting Mode | clip-on |
Net Weight | 0.12 kg |
Network Frequency | 50/60 Hz |
Product Compatibility | C60 accessories C60 auxiliary |
Tightening Torque | 3.5-3.5 N.m downside power circuit: 3.5-3.5 N.m upside |
Width | 18 mm |
ENVIRONMENT | |
Ambient Air Temperature For Operation | -25-60 °C |
Ambient Air Temperature For Storage | -40-70 °C |
IP Degree Of Protection | IP20 conforming to IEC 60529 |
Operating Altitude | 2000 m |
Overvoltage Category | IV |
Relative Humidity | 95-95 % at 55-55 °C |
Standards | EN 60898 EN/IEC 60947-2 |
Tropicalisation | 2 conforming to IEC 60068-1 |
OTHER | |
Poles Description | 1P |
[Us] Rated Supply Voltage | C60 |