Electronic Pressure Sensors, Pressure Sensors XM, XMLR 16 Bar, 1/4
Telemecanique
SKU
SE_XMLR016G1N26
Model
XMLR016G1N26
SGD $520.02
Short description of XMLR016G1N26
Sensors for pressure control
Country of Origin
Switzerland
range of product : OsiSense XM
-  product or component type : Electronic pressure sensors
-  pressure sensor type : Pressure transmitter
-  pressure switch type of operation : Pressure transmitter with 1 switching output
-  device short name : XMLR
-  pressure rating : 16 bar1599.58 kPa
-  maximum permissible accidental pressure : 6205.28 kPa6.2 MPa62 bar
-  destruction pressure : 62 bar6205.28 kPa6.2 MPa
-  controlled fluid : Fresh water (0…80 °C)Air (-20…80 °C)Hydraulic oil (-20…80 °C)Refrigeration fluid (-20…80 °C)
-  fluid connection type : 1/4"
-  18 NPT (female)
-  [Us] rated supply voltage : 24 V DC SELV (voltage limits :  17…33 V)
-  product or component type : Electronic pressure sensors
-  pressure sensor type : Pressure transmitter
-  pressure switch type of operation : Pressure transmitter with 1 switching output
-  device short name : XMLR
-  pressure rating : 16 bar1599.58 kPa
-  maximum permissible accidental pressure : 6205.28 kPa6.2 MPa62 bar
-  destruction pressure : 62 bar6205.28 kPa6.2 MPa
-  controlled fluid : Fresh water (0…80 °C)Air (-20…80 °C)Hydraulic oil (-20…80 °C)Refrigeration fluid (-20…80 °C)
-  fluid connection type : 1/4"
-  18 NPT (female)
-  [Us] rated supply voltage : 24 V DC SELV (voltage limits :  17…33 V)
MAIN SPECIFICATIONS | |
---|---|
Analogue Input Number | 24 V DC SELV (voltage limits: 17-33 V) |
Contacts Type And Composition | NO/NC programmable |
Discrete Input Number | NO/NC programmable |
Discrete Output Type | solid state NPN, NO/NC programmable |
Display Type | 4 digits 7 segments |
Measurement Accuracy | <= 0.6 % of the measuring range |
Pressure Sensor Size | 16 bar 232 psi |
Pressure Sensor Type | pressure transmitter |
Product Or Component Type | electronic pressure sensors |
Range Of Product | OsiSense XM |
Thread Type | 0...50 s in steps of 1 second |
Adjustable Range Of Switching Point On Falling Pressure | 0.08-1.55 MPa 0.8-15.5 bar 11.6-225 psi |
Adjustable Range Of Switching Point On Rising Pressure | 0.128-1.6 MPa 1.28-16 bar 18.6-232 psi |
Analogue Output Function | 4...20 mA |
Device Short Name | XMLR |
Fluid Connection Type | 1/4" - 18 NPT (female) |
Materials In Contact With Fluid | 316L stainless steel ceramic fluorocarbon FKM (Viton) |
Pressure Switch Type Of Operation | pressure transmitter with 1 switching output |
Range Name | OsiSense XM |
Scale Type | fixed differential |
Type Of Output Signal | analogue + discrete |
COMPLEMENTARY | |
Analogue Output Number | 4 digits 7 segments |
Analogue Output Type | 16 bar 232 psi |
Time Delay | <= 0.6 % of the measuring range |
Time Delay Range | 0...50 s in steps of 1 second |
[Ics] Rated Service Breaking Capacity | solid state NPN, NO/NC programmable |
Accuracy | <= 1 % of the measuring range |
Controlled Fluid | air,hydraulic oil,fresh water,refrigeration fluid air (-20-80 °C) fresh water (0-80 °C) hydraulic oil (-20-80 °C) refrigeration fluid (-20-80 °C) |
Current Consumption | <= 50 mA |
Depth | 42 mm |
Destruction Pressure | 6.2 MPa 62 bar 900 psi |
Display Accuracy | <= 1 % of the measuring range |
Display Response Time Type | fast 50 ms normal 200 ms slow 600 ms |
Drift Of The Sensitivity | +/- 0.03 % of measuring range/°C |
Drift Of The Zero Point | +/- 0.1 % of measuring range/°C |
Electrical Connection | male connector M12, 4 pins |
Front Material | polyester |
Height | 100 mm |
Housing Material | 316L stainless steel polyacrylamide |
Hysteresis | <= 0.2 % of the measuring range |
Linearity Error | <= 0.5 % of the measuring range |
Local Signalling | 1 LED (yellow) for light ON when switch is actuated |
Marking | CE |
Maximum Delay First Up | 300 ms |
Maximum Permissible Accidental Pressure | 6.2 MPa 62 bar 900 psi |
Maximum Switching Current | 250 mA |
Maximum Voltage Drop | 2 V |
Mechanical Durability | 10000000 cycles |
Minimum Differential Travel | 0.48 bar 48 kPa 7 psi |
Net Weight | 0.212 kg |
Operating Position | any position, but disposals can falsified the measurement in case of upside down mounting |
Protection Type | overload protection overvoltage protection reverse polarity short-circuit protection |
Repeat Accuracy | <= 0.2 % of the measuring range |
Response Time On Output | <= 10 ms for analog output <= 5 ms for discrete output |
Temperature Of Controlled Fluid | -20-80 °C |
Width | 41 mm |
[Uimp] Rated Impulse Withstand Voltage | 0.5 kV DC |
ENVIRONMENT | |
Safety Level | pressure transmitter |
Ambient Air Temperature For Operation | -20-80 °C |
Ambient Air Temperature For Storage | -40-80 °C |
Electromagnetic Compatibility | electrical fast transient/burst immunity test: 2 kV conforming to EN/IEC 61000-4-4 electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2 immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6 surge immunity test: 1 kV conforming to EN/IEC 61000-4-5 susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3 |
IP Degree Of Protection | IP65 conforming to EN/IEC 60529 IP67 conforming to EN/IEC 60529 |
Product Certifications | cULus EAC |
Shock Resistance | 50 gn conforming to EN/IEC 60068-2-27 |
Standards | EN/IEC 61326-2-3 UL 61010-1 |
Vibration Resistance | 20 gn (f= 10-2000 Hz) conforming to EN/IEC 60068-2-6 |
OTHER | |
Poles Description | electronic pressure sensors |
[Us] Rated Supply Voltage | 24 V DC SELV (voltage limits: 17-33 V) |
Write Your Own Review