Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

Variable Speed Drive ATV212 - 22kW - 30hp - 480V - 3ph - EMC - IP21

Schneider
SKU
SE_ATV212HD22N4
Model
ATV212HD22N4
SGD $2,818.58

Short description of ATV212HD22N4

ATV212 22KW 30HP 480V TRI CEM IP20
Country of Origin
China
-
+

UOM: Piece

In stock
In Stock 3
Backorder Leadtime: 2 Days

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
variable speed drive ATV212
-  22kW
-  30hp
-  480V
-  3ph
-  EMC
-  IP21.
Label :  Altivar 212
-  range of product :  Altivar 212
-  [Us] rated supply voltage :  380...480 V
-  15...10 %
-  supply voltage limits :  323-528 V
-  supply frequency :  50...60 Hz
-  5...5 %
-  network frequency :  47.5...63 Hz
-  EMC filter :  Class C2 EMC filter integrated
-  line current :  33.1 A at 480 V, 41.6 A at 380 V
-  product or component type :  variable speed drive
-  device short name :  ATV212
-  product destination :  asynchronous motors
-  product specific application :  pumps and fans in HVAC
-  assembly style :  with heat sink
-  network number of phases :  3 phases
-  motor power kW :  22 kW
-  motor power hp :  30 hp
-  Range Presentation :  The Altivar 212 is a variable speed drive for 3-phase asynchronous motors from 0.75 kW to 75 kW. It is specifically intended for the most commonly encountered fluid management applications in tertiary sector buildings (HVAC) :  heating, ventilation, air conditioning and pumping. Due to its eco
- energy based design, energy savings of up to 70% can be achieved compared to a traditional control system.Characteristics : 
-  Altivar 212 covers motor powers between 0.75 kW and 75 kW on the following supplies : 
•200…240V 3-phase, from 0.75 kW to 30 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, IP 21
•380…480V 3-phase, from 0.75 kW to 75 kW, UL Type 12/IP 55
-  Speed range :  1 : 50
-  Transient overtorque :  110%
-  60 s.
-  Integrated EMC filters, categories C1 to C3 depending on model
-  Communication bus most commonly used on the market integrated :  Modbus, METASYS N2®, APOGEE FLN P1® and BACnet®. Optional :  LonWorks
-  Complies to international standards and certifications :  UL, CSA, C
- Tick and NOM
-  Antiharmonic technology enables a THDI 30% to be achieved
-  Range Benefits :  Centred on Centralised Technical Management
-  Instant viewing of the energy consumption.
-  Detection of failures for quick intervention :  belt breakage, pump running dry, phase failure, supply fault, etc.
-  Preventative maintenance for reducing costs and optimising the equipment :  fault alert, operating time, etc.
-  Connection to building supervision network using embedded protocols.
Centred on user-friendliness
-  Tools for installing, parametering and viewing the installation (remote graphic terminal in 6 languages, Multi-Loader, Bluetooth and SoMove Mobile).
-  Compact size.
-  Simple maintenance.
Centred on protection
-  Continuity of service assured.
-  Dedicated “Building” series functions (fire mode, register monitoring, mechanical protection function, etc.
-  Integrated EMC filter, antiharmonic technology (THDI ˜ 30%).
-  Range Application Presentation :  Ventilation : 
-  Less noise pollution (airdraulic noise, motor noise, etc.).
-  Detection of transmission component breakage.
-  Smoke extraction :  forced start with fault inhibition.
-  Automatic restart.
-  Allows register management. Heating and Air conditioning : 
-  Optimise control in fluid processing.
-  Use of PID controller (temperature, flow rate, pressure, etc.).
-  Adjustable flow rates for better energy management.
-  Suppression of mechanical resonance. Pumping : 
-  Detection of underload/overload, pump running dry.
-  Multi-motor configuration.
-  Limitation of operating time at low speed.
-  Sleep/Wake function.
-  Pressure surge suppression for prolonging the life of the installation.
MAIN SPECIFICATIONS
Analog/digital ConversionFM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
Analogue Input Number2
Analogue Input Range2
Discrete Output Typeconfigurable relay logic: (FLA, FLC) NO - 100000 cycles
configurable relay logic: (FLB, FLC) NC - 100000 cycles
configurable relay logic: (RY, RC) NO - 100000 cycles
Display Type2-wire RS 485
Measurement Accuracy1 open style
1 RJ45
Physical Interface2-wire RS 485
Product Or Component Typevariable speed drive
Range Of ProductAltivar 212
Communication Port ProtocolAPOGEE FLN
BACnet
LonWorks
METASYS N2
Modbus
Device Short NameATV212
EAN133606480322549
EMC FilterClass C2 EMC filter integrated
Line Current33.1 A at 480 V
41.6 A at 380 V
Motor Power Hp30 hp
Network Number Of Phases3 phases
Product Specific Applicationpumps and fans in HVAC
Range NameAltivar 212
Speed Range1-10
COMPLEMENTARY
Analogue Input TypeVIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits
VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm
VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits
Analogue Output Number1
Analogue Output TypeFM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits
FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits
Connector Type1 open style
1 RJ45
Discrete Output Number2
Output Voltage<= power supply voltage
Port Ethernet2
[Ics] Rated Service Breaking Capacityconfigurable relay logic: (FLA, FLC) NO - 100000 cycles
configurable relay logic: (FLB, FLC) NC - 100000 cycles
configurable relay logic: (RY, RC) NO - 100000 cycles
Acceleration And Deceleration Rampsautomatic based on the load
linear adjustable separately from 0.01 to 3200 s
Accuracy+/- 0.6 % (VIA) for a temperature variation 60 °C
+/- 0.6 % (VIB) for a temperature variation 60 °C
+/- 1 % (FM) for a temperature variation 60 °C
Air Flow214 m3/h
Apparent Power33.2 kVA at 380 V
Assembly Stylewith heat sink
Asynchronous Motor Control Profileflux vector control without sensor, standard
voltage/frequency ratio - Energy Saving, quadratic U/f
voltage/frequency ratio, 2 points
voltage/frequency ratio, 5 points
voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
Braking To Standstillby DC injection
Communication Servicemonitoring inhibitable
read device identification (43)
read holding registers (03) 2 words maximum
time out setting from 0.1 to 100 s
write multiple registers (16) 2 words maximum
write single register (06)
Continuous Output Current43.5 A at 380 V
43.5 A at 460 V
Data Format8 bits, 1 stop, odd even or no configurable parity
Depth214 mm
Discrete Input Logicnegative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)
positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1)
Discrete Input TypeF programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm
Electrical ConnectionL1/R, L2/S, L3/T: terminal 50-50 mm² / AWG 1/0
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5-2.5 mm² / AWG 14
Frequency Resolutionanalog input: 0.024/50 Hz
display unit: 0.1 Hz
Functionalitymid
Height420 mm
Insulation Resistance>= 1 mOhm 500 V DC for 1 minute
Isolationelectrical between power and control
Linearity ErrorFM: +/- 0.2 % for output
VIA: +/- 0.15 % of maximum value for input
VIB: +/- 0.15 % of maximum value for input
Local Signalling1 LED (red) for DC bus energized
MarkingCE
Maximum Switching Current2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R)
Maximum Transient Current47.9 A for 60 s
Minimum Switching Current3 mA at 24 V DC for configurable relay logic
Motor Power KW22 kW
Motor Slip Compensationadjustable
automatic whatever the load
not available in voltage/frequency ratio motor control
Motor Starter Typevariable speed drive
Net Weight26.4 kg
Network Frequency47.5...63 Hz
Nominal Switching Frequency8 kHz
Number Of Addresses1-247
Operating Positionvertical +/- 10 degree
Option Cardcommunication card for LonWorks
Power Dissipation In W626 W
Power Range15-25 kW at 380-440 V 3 phases
15-25 kW at 480-500 V 3 phases
Product Destinationasynchronous motors
Prospective Line Isc22 kA
Protection Typeagainst exceeding limit speed: drive
against input phase loss: drive
break on the control circuit: drive
input phase breaks: drive
line supply overvoltage and undervoltage: drive
line supply undervoltage: drive
motor phase break: motor
overcurrent between output phases and earth: drive
overheating protection: drive
overvoltages on the DC bus: drive
short-circuit between motor phases: drive
thermal power stage: drive
thermal protection: motor
with PTC probes: motor
Response TimeFLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
FM 2 ms, tolerance +/- 0.5 ms for analog output(s)
RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)
Sampling Duration2 ms +/- 0.5 ms F discrete
2 ms +/- 0.5 ms R discrete
2 ms +/- 0.5 ms RES discrete
22 ms +/- 0.5 ms VIB analog
3.5 ms +/- 0.5 ms VIA analog
Specific ApplicationHVAC
Speed Accuracy+/- 10 % of nominal slip 0.2 Tn to Tn
Speed Drive Output Frequency0.5-200 Hz
Supplyinternal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection
internal supply: 24 V DC (21-27 V), <200 A, protection type: overload and short-circuit protection
Supply Frequency50...60 Hz - 5...5 %
Supply Voltage Limits323-528 V
Switching Frequency6...16 kHz adjustable
8...16 kHz with derating factor
Tightening Torque0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
24 N.m, 212 lb.in (L1/R, L2/S, L3/T)
Torque Accuracy+/- 15 %
Transient Overtorque120-120 % of nominal motor torque +/- 10 % for 60 s
Transmission FrameRTU
Transmission Rate9600 bps or 19200 bps
Type Of Cablewith UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC
without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC
without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR
Type Of Polarizationno impedance
Width240 mm
ENVIRONMENT
Ambient Air Temperature For Operation-10-40 °C (without derating)
40-50 °C (with derating factor)
Ambient Air Temperature For Storage-25-70 °C
Dielectric Strength3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Electromagnetic Compatibility1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3
voltage dips and interruptions immunity test conforming to IEC 61000-4-11
Environmental Characteristicclasses 3C1 conforming to IEC 60721-3-3
classes 3S2 conforming to IEC 60721-3-3
IP Degree Of ProtectionIP20 on upper part without blanking plate on cover conforming to EN/IEC 60529
IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1
IP21 conforming to EN/IEC 60529
IP21 conforming to EN/IEC 61800-5-1
IP41 on upper part conforming to EN/IEC 60529
IP41 on upper part conforming to EN/IEC 61800-5-1
IP21
Noise Level59.9 dB conforming to 86/188/EEC
Operating Altitude<= 1000 m without derating
1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
Pollution Degree3 conforming to IEC 61800-5-1
Product CertificationsCSA
C-Tick
NOM 117
UL
Regulation Loopadjustable PI regulator
Relative Humidity5-95 % without condensation conforming to IEC 60068-2-3
5-95 % without dripping water conforming to IEC 60068-2-3
Shock Resistance15 gn for 11 ms conforming to IEC 60068-2-27
StandardsEN 55011 class A group 1
EN 61800-3
EN 61800-3 category C2
EN 61800-3 category C3
EN 61800-3 environments 1 category C1
EN 61800-3 environments 1 category C2
EN 61800-3 environments 1 category C3
EN 61800-3 environments 2 category C1
EN 61800-3 environments 2 category C2
EN 61800-3 environments 2 category C3
EN 61800-5-1
IEC 61800-3
IEC 61800-3 category C2
IEC 61800-3 category C3
IEC 61800-3 environments 1 category C1
IEC 61800-3 environments 1 category C2
IEC 61800-3 environments 1 category C3
IEC 61800-3 environments 2 category C1
IEC 61800-3 environments 2 category C2
IEC 61800-3 environments 2 category C3
IEC 61800-5-1
UL type 1
Vibration Resistance1 gn (f= 13-200 Hz) conforming to EN/IEC 60068-2-8
1.5 mm (f= 3-13 Hz) conforming to EN/IEC 60068-2-6
OTHER
Poles Descriptionvariable speed drive
[Us] Rated Supply Voltage380...480 V - 15...10 %
Write Your Own Review
You're reviewing:Variable Speed Drive ATV212 - 22kW - 30hp - 480V - 3ph - EMC - IP21
Your Rating