Module XPSATR - Emergency Stop and Protective Guard - 115-230V AC, Time Delay 3s.

Schneider
SKU
SE_XPSATR3953P
Model
XPSATR3953P

Obsolete

Short description of XPSATR3953P

Safety Modules
Obsolete
*All information are subjected to changes without prior notice.
range of product : Preventa Safety automation
-  product or component type : Preventa safety module
-  safety module name : XPSATR
-  safety module application : For emergency stop and protective guard applications
-  function of module : Emergency stop monitoring 2-channel wiringProtective guard monitoringEmergency stop monitoring 1-channel wiring
-  safety level : Can reach PL e/category 4 instantaneous safety outputs conforming to EN/ISO 13849-1Can reach SILCL 3 time delay safety outputs conforming to EN/IEC 62061
-  safety reliability data : DC > 99 % conforming to EN/ISO 13849-1MTTFd = 85 years conforming to EN/ISO 13849-1PFHd = 2E
- 9 1/h conforming to EN/IEC 62061
-  type of start : AutomaticManual
-  connections
-  terminals : Captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezelCaptive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezelCaptive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezelCaptive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid or flexible without cable endCaptive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid or flexible without cable endCaptive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with bezel
-  output type : Relay instantaneous opening, 3 NO circuit(s), volt
- freeRelay time delay opening, 3 NO circuit(s), volt
- free
-  number of additional circuits : 1 NC
-  [Us] rated supply voltage : 115...230 V AC
-  15...10 %
MAIN SPECIFICATIONS
Analogue Input Number115...230 V AC - 15...10 %
Breaking Capacity3 A at 24 V (DC-13) for relay output
Continuous Powercan reach PL e/category 4 instantaneous safety outputs conforming to EN/ISO 13849-1
can reach SILCL 3 time delay safety outputs conforming to EN/IEC 62061
Product Or Component TypePreventa safety module
Range Of ProductPreventa Safety automation
Thread Type0.1...3 s
[Uc] Control Circuit Voltage24 V DC
Function Of Moduleemergency stop monitoring 1-channel wiring
emergency stop monitoring 2-channel wiring
protective guard monitoring
Mounting Support35 mm symmetrical DIN rail
Number Of Additional Circuits1 NC
Range NamePreventa XPS
Safety Module Applicationfor emergency stop and protective guard applications
Safety Module NameXPSATR
Type Of Startautomatic
manual
COMPLEMENTARY
Interlocked Device3 A at 24 V (DC-13) for relay output
Product Namerelay instantaneous opening, 3 NO circuit(s), volt-free
relay time delay opening, 3 NO circuit(s), volt-free
Time Delay Range0.1...3 s
Associated Fuse Rating6 A gG for instantaneous and time delay outputs conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Connections - Terminalscaptive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid or flexible without cable end
captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 1.5 mm² flexible with cable end, with bezel
captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel
captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid or flexible without cable end
captive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel
captive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with bezel
Input Protection Typeinternal, electronic
Local Signalling5 LEDs
Maximum Power Consumption In VA6.3 VA
Maximum Power Consumption In W3.2 W AC
Maximum Response Time On Input Open20 ms
Minimum Output Current10 mA for relay output
Minimum Output Voltage17 V for relay output
Output Thermal Current6 A for instantaneous and time delay outputs
Output Typerelay instantaneous opening, 3 NO circuit(s), volt-free
relay time delay opening, 3 NO circuit(s), volt-free
Safety Reliability DataDC > 99 % conforming to EN/ISO 13849-1
MTTFd = 85 years conforming to EN/ISO 13849-1
PFHd = 2E-9 1/h conforming to EN/IEC 62061
Supply Frequency50/60 Hz
Synchronisation Time Between Inputs1 s
[Ith] Conventional Free Air Thermal Current8 A
[Uimp] Rated Impulse Withstand Voltage4 kV overvoltage category III conforming to EN/IEC 60947-5-1, DIN VDE 0110 parts 1 & 2
[Ui] Rated Insulation Voltage300 V
ENVIRONMENT
Safety Levelcan reach PL e/category 4 instantaneous safety outputs conforming to EN/ISO 13849-1
can reach SILCL 3 time delay safety outputs conforming to EN/IEC 62061
Ambient Air Temperature For Operation-25-55 °C
Ambient Air Temperature For Storage-25-75 °C
IP Degree Of ProtectionIP20 (terminals) conforming to EN/IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529
Product CertificationsCSA
TÜV
UL
StandardsEN 50156-1
EN 60204-1
EN 62061
EN/IEC 60947-5-1
EN/IEC 61496-1
EN/ISO 13849-1
OTHER
Poles DescriptionPreventa safety module
[Us] Rated Supply Voltage115...230 V AC - 15...10 %