Singapore GST will increase from 8% to 9%

(Effective from Jan 1, 2024)

Electgo: Your trusted Source for Electrical Components in Singapore

An Authorized Supplier Offering a Comprehensive Range of Electrical Component Categories

Loading...

Module XPSAR - Emergency Stop - 230 V AC.

Schneider
SKU
SE_XPSAR371144P
Model
XPSAR371144P

Obsolete

Short description of XPSAR371144P

Safety Modules
Obsolete
*All information are subjected to changes without prior notice.
range of product : Preventa Safety automation
-  product or component type : Preventa safety module
-  safety module name : XPSAR
-  safety module application : For emergency stop, switch and safety light curtain monitoring
-  function of module : Monitoring of a movable guardEmergency stop with 2 NC contacts monitoring 2-channel wiringMultiple emergency stop monitoring 2-channel wiringEmergency stop monitoring 1-channel wiringMonitoring of a movable guard associated with 2 switches and automatic startMonitoring of electro
- sensitive protection equipment (ESPE)
-  safety level : Can reach PL e/category 4 conforming to EN/ISO 13849-1Can reach SILCL 3 conforming to EN/IEC 62061
-  safety reliability data : DC > 99 % conforming to EN/ISO 13849-1MTTFd = 277.8 years conforming to EN/ISO 13849-1PFHd = 2.22E
- 9 1/h conforming to EN/IEC 62061
-  type of start : Configurable
-  connections
-  terminals : Captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid with cable end, with double bezelCaptive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid with cable end, with double bezelCaptive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1.5 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezelCaptive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
-  output type : Relay instantaneous opening, 7 NO circuit(s), volt
- free
-  number of additional circuits : 2 NC + 4 solid state outputs
-  [Us] rated supply voltage : 230 V AC
-  15...10 %24 V DC-15...10 %
MAIN SPECIFICATIONS
Analogue Input Number230 V AC - 15...10 %
24 V DC - 15...10 %
Breaking Capacity2 A at 24 V (DC-13) time constant: 50 ms for relay output
20 mA at 24 V
360 VA holding AC-15 C300 relay output
3600 VA inrush AC-15 C300 relay output
Continuous Powercan reach PL e/category 4 conforming to EN/ISO 13849-1
can reach SILCL 3 conforming to EN/IEC 62061
Product Or Component TypePreventa safety module
Range Of ProductPreventa Safety automation
Thread Type0...30 s
[Uc] Control Circuit Voltage24 V DC
Function Of Moduleemergency stop monitoring 1-channel wiring
emergency stop with 2 NC contacts monitoring 2-channel wiring
monitoring of a movable guard
monitoring of a movable guard associated with 2 switches and automatic start
monitoring of electro-sensitive protection equipment (ESPE)
multiple emergency stop monitoring 2-channel wiring
Mounting Support35 mm symmetrical DIN rail
Number Of Additional Circuits2 NC + 4 solid state outputs
Range NamePreventa XPS
Safety Module Applicationfor emergency stop, switch and safety light curtain monitoring
Safety Module NameXPSAR
Type Of Startconfigurable
COMPLEMENTARY
Interlocked Device2 A at 24 V (DC-13) time constant: 50 ms for relay output
20 mA at 24 V
360 VA holding AC-15 C300 relay output
3600 VA inrush AC-15 C300 relay output
Product Namerelay instantaneous opening, 7 NO circuit(s), volt-free
Time Delay Range0...30 s
Associated Fuse Rating10 A fast blow for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
6 A gG or gL for relay output conforming to EN/IEC 60947-5-1, DIN VDE 0660 part 200
Connections - Terminalscaptive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, removable terminal block, 1 x 0.2...1 x 2.5 mm² solid with cable end, with double bezel
captive screw clamp terminals, removable terminal block, 1 x 0.25...1 x 2.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1 mm² solid with cable end, with double bezel
captive screw clamp terminals, removable terminal block, 2 x 0.2...2 x 1.5 mm² flexible with cable end, with double bezel
captive screw clamp terminals, removable terminal block, 2 x 0.25...2 x 1 mm² flexible with cable end, with double bezel
captive screw clamp terminals, removable terminal block, 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel
Current Consumption30 mA at 24 V DC on power supply
Input Protection Typeinternal, electronic
Local Signalling4 LEDs
Maximum Line Resistance50 Ohm
Maximum Power Consumption In VA9 VA AC
Maximum Power Consumption In W4 W DC
Maximum Response Time On Input Open20 ms
Minimum Output Current170 mA for relay output
Minimum Output Voltage17 V for relay output
Net Weight0.4 kg
Output Thermal Current10 A per relay for relay output
Output Typerelay instantaneous opening, 7 NO circuit(s), volt-free
Safety Reliability DataDC > 99 % conforming to EN/ISO 13849-1
MTTFd = 277.8 years conforming to EN/ISO 13849-1
PFHd = 2.22E-9 1/h conforming to EN/IEC 62061
Supply Frequency50/60 Hz
Synchronisation Time Between Inputs100 ms
[Ith] Conventional Free Air Thermal Current40 A
[Uimp] Rated Impulse Withstand Voltage4 kV overvoltage category III conforming to DIN VDE 0110 part 1
4 kV overvoltage category III conforming to IEC 60947-5-1
[Ui] Rated Insulation Voltage300 V (pollution degree 2) conforming to DIN VDE 0110 part 1
300 V (pollution degree 2) conforming to IEC 60947-5-1
ENVIRONMENT
Safety Levelcan reach PL e/category 4 conforming to EN/ISO 13849-1
can reach SILCL 3 conforming to EN/IEC 62061
Ambient Air Temperature For Operation-10-55 °C
Ambient Air Temperature For Storage-25-85 °C
IP Degree Of ProtectionIP20 (terminals) conforming to EN/IEC 60529
IP40 (enclosure) conforming to EN/IEC 60529
Product CertificationsCSA
TÜV
UL
StandardsEN 1088/ISO 14119
EN/IEC 60204-1
EN/IEC 60947-5-1
EN/ISO 13850
OTHER
Poles DescriptionPreventa safety module
[Us] Rated Supply Voltage230 V AC - 15...10 %
24 V DC - 15...10 %