Contactor, TeSys K, 3P, AC-3, lt or eq to 440V 9A, 1 NC aux., 220 to 230VAC coil
Schneider
SKU
SE_LC1K0901M7
Model
LC1K0901M7
SGD $25.76
Short description of LC1K0901M7
LC1K0901M7 is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 220V 50/60Hz AC coil and 1NC auxiliary contact. LC1K0901M7 is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 4kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it includes a 220V 50/60Hz AC coil and 1NC built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Provides a control circuit compatible with 50Hz and 60Hz supplies and 1NC built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).
Country of Origin
Indonesia
TeSys K is a compact contactor range with a wide variety of coil voltage and terminal connection options
The offer features specific versions for railway (TeSys S207) and electrodomestic (TeSys S335) applications
One of the smallest contactor offerings in the market
The range delivers strong performance for its compact size and promises seamless integration in all applications.
Widely used for industry, infrastructure and building applications
MAIN | |
---|---|
Range | TeSys |
Product Or Component Type | Contactor |
Device Short Name | LC1K |
Device Application | Control |
Contactor Application | Motor control Resistive load |
COMPLEMENTARY | |
Utilisation Category | AC-3 AC-3e AC-1 AC-4 |
Poles Description | 3P |
Power Pole Contact Composition | 3 NO |
[Ue] Rated Operational Voltage | Power circuit <= 690 V AC <= 400 Hz Signalling circuit <= 690 V AC <= 400 Hz |
[Ie] Rated Operational Current | 9 A 140 °F (60 °C)) <= 440 V AC AC-3 power circuit 9 A 140 °F (60 °C)) <= 440 V AC AC-3e power circuit 20 A 140 °F (60 °C)) <= 690 V AC AC-1 power circuit |
Control Circuit Type | AC 50/60 Hz |
[Uc] Control Circuit Voltage | 220...230 V AC 50/60 Hz |
Motor Power KW | 2.2 kW 220...230 V AC 50/60 Hz AC-3 4 kW 380...415 V AC 50/60 Hz AC-3 4 kW 440/690 V AC 50/60 Hz AC-3 2.2 kW 220...230 V AC 50/60 Hz AC-3e 4 kW 380...415 V AC 50/60 Hz AC-3e 4 kW 440/690 V AC 50/60 Hz AC-3e 2.2 kW 220...230 V AC 50/60 Hz AC-4 4 kW 380...415 V AC 50/60 Hz AC-4 4 kW 440/690 V AC 50/60 Hz AC-4 |
Auxiliary Contact Composition | 1 NC |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Overvoltage Category | III |
[Ith] Conventional Free Air Thermal Current | 20 A 140 °F (60 °C) power circuit 10 A 122 °F (50 °C) signalling circuit |
Irms Rated Making Capacity | 110 A AC power circuit IEC 60947 110 A AC signalling circuit IEC 60947 |
Rated Breaking Capacity | 110 A 220...230 V IEC 60947 110 A 380...400 V IEC 60947 110 A 415 V IEC 60947 110 A 440 V IEC 60947 80 A 500 V IEC 60947 70 A 660...690 V IEC 60947 |
[Icw] Rated Short-time Withstand Current | 90 A 122 °F (50 °C) - 1 s power circuit 85 A 122 °F (50 °C) - 5 s power circuit 80 A 122 °F (50 °C) - 10 s power circuit 60 A 122 °F (50 °C) - 30 s power circuit 45 A 122 °F (50 °C) - 1 min power circuit 40 A 122 °F (50 °C) - 3 min power circuit 20 A 122 °F (50 °C) - >= 15 min power circuit 80 A - 1 s signalling circuit 90 A - 500 ms signalling circuit 110 A - 100 ms signalling circuit |
Associated Fuse Rating | 25 A gG <= 440 V power circuit 25 A aM power circuit 10 A gG signalling circuit IEC 60947 10 A gG signalling circuit VDE 0660 |
Average Impedance | 3 mOhm - Ith 20 A 50 Hz power circuit |
Insulation Resistance | > 10 MOhm signalling circuit |
Inrush Power In VA | 30 VA 68 °F (20 °C)) |
Hold-in Power Consumption In VA | 4.5 VA 68 °F (20 °C)) |
Heat Dissipation | 1.3 W |
Control Circuit Voltage Limits | Operational 0.8...1.15 Uc 122 °F (50 °C)) Drop-out >= 0.20 Uc 122 °F (50 °C)) |
Connections - Terminals | screw clamp terminals 1 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 1 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.00…0.00 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.00…0.01 in² (1.5…4 mm²)solid screw clamp terminals 2 0.00…0.01 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.00…0.00 in² (0.34…1.5 mm²)flexible with cable end |
Maximum Operating Rate | 3600 cyc/h |
Auxiliary Contacts Type | Instantaneous 1 NC |
Signalling Circuit Frequency | <= 400 Hz |
Minimum Switching Current | 5 mA signalling circuit |
Minimum Switching Voltage | 17 V signalling circuit |
Operating Time | 10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing |
Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Non Overlap Distance | 0.02 in (0.5 mm) |
Mechanical Durability | 10 Mcycles |
Electrical Durability | 1.3 Mcycles 9 A AC-3 <= 440 V 1.3 Mcycles 9 A AC-3e <= 440 V 0.16 Mcycles 20 A AC-1 <= 690 V 0.02 Mcycles 54 A AC-4 <= 440 V |
Mechanical Robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 |
Height | 2.28 in (58 mm) |
Width | 1.77 in (45 mm) |
Depth | 2.24 in (57 mm) |
ENVIRONMENT | |
Standards | EN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 |
Product Certifications | CB Scheme CCC UL CSA EAC CE UKCA |
Protective Treatment | TC IEC 60068 TC DIN 50016 |
Operating Altitude | 6561.68 ft (2000 m) without derating |
Flame Retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
ORDERING AND SHIPPING DETAILS | |
Category | 22326-CTR,K-LINE,AC,OPEN,NONREV |
Discount Schedule | I12 |
GTIN | 3389110363418 |
Returnability | No |
Country Of Origin | FR |
Write Your Own Review