F204 B-40/0.03 Residual Current Circuit Breaker

ABB
SKU
AB_2CSF204592R1400
Model
F204-B-40/0.03

Obsolete

Short description of F204 B 40/0.03

F204 B-40/0.03 Residual Current Circuit Breaker
Obsolete
*All information are subjected to changes without prior notice.
The RCCBs F200 series assures protection to people and installations against fault current to earth. A large offer for standard instantaneous and selective AC and A types is completed with some configurations for special applications. This product is particularly suitable for the protection against smooth d.c. earth fault currents.
MAIN SPECIFICATION
ABB Global IDABB2CSF204592R1400
Business Area (Master Data) NameElectrification
Catalog DescriptionF204 B-40/0,03 Residual Current Circuit Breaker
Division (Master Data) NameSmart Buildings
EAN8012542358336
Rated Insulation Voltage (Ui)500 volt
SKU ID2CSF204592R1400
TECHNICAL
Accessories AvailableYes
Connecting CapacityBusbar 10 mm²
Rigid 25 ... 25 mm²
Flexible 25 ... 25 mm²
Electrical Endurance10000 cycle
Housing TypeInsulation group I - II, RAL 7035
Maximum Surge Current3 kA
Operating CharacteristicInstantaneous
Options ProvidedNone
Pollution Degree2
Position Of Neutral TerminalsRight
Power Lossat Rated Operating Conditions per Pole 1.81 W
Power Supply ConnectionArbitrary
Product NameResidual Current Circuit Breaker
Rated Cross-Section4 - Multi-Wired 0...25 mm²
1 - Solid-Core 25...25 mm²
Rated Frequency (f)50 / 60 Hz
StandardsIEC/EN 61008
TECHNICAL UL/CSA
Short-Circuit Current Rating (SCCR)0.03 A
DIMENSIONS
Built-In Depth (t2)69 mm
ORDERING
Minimum Order Quantity1 piece
Selling Unit Of Measurepiece
ENVIRONMENTAL
Ambient Temperature-25...55 °C
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
CN885363030
E-Number (Finland)3210594
E-Number (Sweden)2160018
EPLAN Catalog TreeElectrical engineering / Protection devices / Ground fault current circuit breaker
ETIM 6EC000003 - Residual current circuit breaker (RCCB)
ETIM 7EC000003 - Residual current circuit breaker (RCCB)
ETIM 8EC000003 - Residual current circuit breaker (RCCB)
Object Classification CodeF
WEEE B2C / B2BBusiness To Consumer
OTHER
Actuator TypeToggle - Insulation group I - II, RAL 5015
Ambient Air TemperatureOperation -25...55 °C
Degree Of ProtectionIP2X
Input Voltage TypeAC
Leakage Current TypeB
Mounting TypeDIN rail
Number Of Poles4
Product Net Width0.072
Rated Conditional Short-Circuit Current (Inc)10 kA
Rated Current (In)40 A
Rated Impulse Withstand Voltage (Uimp)4 kilovolt
Rated Operational Voltage230/400 V
Rated Residual Current30 mA
Rated Service Short-Circuit Breaking Capacity (Ics)1 kA
Rated Voltage (Ur)230/400 V
Type Of Residual CurrentB type
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Width In Number Of Modular Spacings4