A210-30-11 110V 50Hz / 110-120V 60Hz Contactor
ABB
SKU
AB_1SFL511001R8411
Model
A210-30-11-84
Obsolete
Short description of A210 30 11 84
A210-30-11 110V 50Hz / 110-120V 60Hz Contactor
Obsolete
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 690 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SFL511001R8411 |
Business Area (Master Data) Name | Electrification |
Catalog Description | A210-30-11 110V 50Hz / 110-120V 60Hz Contactor |
Division (Master Data) Name | Smart Power |
EAN | 7320500203330 |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt acc. to UL/CSA 600 volt |
SKU ID | 1SFL511001R8411 |
TECHNICAL | |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 60 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 65 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 1350 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 1550 V·A |
Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 1 x 1 .... 4 mm² |
Connecting Capacity Main Circuit | Bar 32 mm² Rigid Al-Cable 120 ... 240 mm² Rigid Cu-Cable 16 ... 240 mm² |
Connecting Terminals (delivered In Open Position) Main Poles | Flat type c/w screws and bolts |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 350 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 2200 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 2000 A |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Mechanical Durability | 5 million |
Operate Time | Between Coil De-energization and NC Contact Closing 7 ... 13 ms Between Coil De-energization and NO Contact Opening 10 ... 16 ms Between Coil Energization and NC Contact Opening 12 ... 30 ms Between Coil Energization and NO Contact Closing 17 ... 35 ms |
Rated Breaking Capacity AC-3 Acc. To IEC 60947-4-1 | 8 x Ie AC-3 |
Rated Frequency (f) | Main Circuit 50 / 60 Hz |
Rated Making Capacity AC-3 Acc. To IEC 60947-4-1 | 10 x Ie AC-3 |
Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A (220 V) 3 Poles in Series, 40 °C 350 A |
Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A (220 V) 3 Poles in Series, 40 °C 350 A |
Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 350 A (220 V) 3 Poles in Series, 40 °C 350 A |
Rated Short-time Withstand Current (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1700 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 1000 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 2500 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 1200 A |
Short-Circuit Protective Devices | gG Type Fuses 400 A |
Terminal Type | Main Circuit: Bars |
TECHNICAL UL/CSA | |
General Use Rating UL/CSA | (600 V AC) 300 A |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 60 hp (208 V AC) Three Phase 60 hp (220 ... 240 V AC) Three Phase 75 hp (440 ... 480 V AC) Three Phase 150 hp (550 ... 600 V AC) Three Phase 200 hp |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Maximum Operating Altitude Permissible | 3000 m |
Resistance To Shock Acc. To IEC 60068-2-27 | Shock Direction: A 5 K40 Shock Direction: B1 5 K40 Shock Direction: B2 5 K40 Shock Direction: C1 5 K40 Shock Direction: C2 5 K40 |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
E-Number (Norway) | 4115174 |
E-Number (Sweden) | 3227873 |
EClass | V11.0 : 27371003 |
ETIM 4 | EC000066 - Magnet contactor, AC-switching |
ETIM 5 | EC000066 - Magnet contactor, AC-switching |
ETIM 6 | EC000066 - Power contactor, AC switching |
ETIM 7 | EC000066 - Power contactor, AC switching |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
Object Classification Code | Q |
UNSPSC | 39121529 |
OTHER | |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C Close to Contactor for Storage -40 ... +70 °C |
Degree Of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Number Of Auxiliary Contacts NC | 1 |
Number Of Auxiliary Contacts NO | 1 |
Number Of Main Contacts NO | 3 |
Number Of Poles | 3 |
Product Net Width | 140 |
Rated Control Circuit Voltage (Uc) | 50 Hz 110 V 60 Hz 110 ... 120 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kilovolt |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 350 No unit (690 V) 55 °C 300 No unit (690 V) 70 °C 240 No unit |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 210 A (440 V) 55 °C 210 A (500 V) 55 °C 210 A (690 V) 55 °C 210 A (380 / 400 V) 55 °C 210 A (220 / 230 / 240 V) 55 °C 210 |
Rated Operational Power AC-3 (Pe) | (415 V) 110 kW (440 V) 110 kW (500 V) 132 kW (690 V) 160 kW (380 / 400 V) 110 kW (220 / 230 / 240 V) 59 kW |
Rated Operational Voltage | Main Circuit 690 V |