A145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
ABB
SKU
AB_1SFL471001R8011
Model
A145-30-11-80
Obsolete
Short description of A145 30 11 80
A145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
Obsolete
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SFL471001R8011 |
Business Area (Master Data) Name | Electrification |
Catalog Description | A145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor |
Division (Master Data) Name | Smart Power |
EAN | 7320500203286 |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt acc. to UL/CSA 600 volt |
SKU ID | 1SFL471001R8011 |
TECHNICAL | |
Coil Consumption | Holding at Max. Rated Control Circuit Voltage 50 Hz 35 V·A Holding at Max. Rated Control Circuit Voltage 60 Hz 40 V·A Pull-in at Max. Rated Control Circuit Voltage 50 Hz 550 V·A Pull-in at Max. Rated Control Circuit Voltage 60 Hz 600 V·A |
Coil Operating Limits | (acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C) |
Connecting Capacity Auxiliary Circuit | Flexible with Ferrule 1x 0.75 ... 2.5 mm² Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm² Flexible 2x0.75 ... 2.5 mm² Solid 2 x 1 ... 4 mm² Stranded 2 x 1 .... 4 mm² |
Connecting Capacity Main Circuit | Bar 24 mm² Rigid Al-Cable 1 x 25 ... 150 mm² Rigid Cu-Cable 1 x 6 ... 185 mm² |
Connecting Terminals (delivered In Open Position) Main Poles | Flat type c/w screws and bolts |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 250 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1500 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1200 A |
Maximum Electrical Switching Frequency | (AC-1) 300 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 300 cycles per hour |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Mechanical Durability | 5 million |
Operate Time | Between Coil De-energization and NC Contact Closing 5 ... 10 ms Between Coil De-energization and NO Contact Opening 9 ... 13 ms Between Coil Energization and NC Contact Opening 8 ... 22 ms Between Coil Energization and NO Contact Closing 13 ... 27 ms |
Rated Breaking Capacity AC-3 Acc. To IEC 60947-4-1 | 8 x Ie AC-3 |
Rated Frequency (f) | Main Circuit 50 / 60 Hz |
Rated Making Capacity AC-3 Acc. To IEC 60947-4-1 | 10 x Ie AC-3 |
Rated Operational Current DC-1 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A (220 V) 3 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-3 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A (220 V) 3 Poles in Series, 40 °C 250 A |
Rated Operational Current DC-5 (Ie) | (110 V) 2 Poles in Series, 40 °C 250 A (220 V) 3 Poles in Series, 40 °C 250 A |
Rated Short-time Withstand Current (Icw) | at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1200 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 280 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 600 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1800 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 800 A |
Short-Circuit Protective Devices | gG Type Fuses 315 A |
Terminal Type | Main Circuit: Bars |
TECHNICAL UL/CSA | |
General Use Rating UL/CSA | (600 V AC) 230 A |
Horsepower Rating UL/CSA | (200 V AC) Three Phase 40 hp (208 V AC) Three Phase 40 hp (220 ... 240 V AC) Three Phase 50 hp (440 ... 480 V AC) Three Phase 100 hp (550 ... 600 V AC) Three Phase 125 hp |
Maximum Operating Voltage UL/CSA | Main Circuit 600 V |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Maximum Operating Altitude Permissible | 3000 m |
Resistance To Shock Acc. To IEC 60068-2-27 | Shock Direction: A 5 K40 Shock Direction: B1 5 K40 Shock Direction: B2 5 K40 Shock Direction: C1 5 K40 Shock Direction: C2 5 K40 |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
E-Number (Finland) | 3709327 |
E-Number (Norway) | 4115096 |
E-Number (Sweden) | 3227854 |
EClass | V11.0 : 27371003 |
ETIM 4 | EC000066 - Magnet contactor, AC-switching |
ETIM 5 | EC000066 - Magnet contactor, AC-switching |
ETIM 6 | EC000066 - Power contactor, AC switching |
ETIM 7 | EC000066 - Power contactor, AC switching |
IDEA Granular Category Code (IGCC) | 4755 >> Contactors |
Object Classification Code | Q |
UNSPSC | 39121529 |
OTHER | |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C Close to Contactor for Storage -40 ... +70 °C |
Degree Of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00 |
Number Of Auxiliary Contacts NC | 1 |
Number Of Auxiliary Contacts NO | 1 |
Number Of Main Contacts NO | 3 |
Number Of Poles | 3 |
Product Net Width | 111.5 |
Rated Control Circuit Voltage (Uc) | 50 Hz 220 ... 230 V 60 Hz 230 ... 240 V |
Rated Impulse Withstand Voltage (Uimp) | Main Circuit 8 kilovolt |
Rated Operational Current AC-1 (Ie) | (1000 V) 40 °C 180 ampere (1000 V) 55 °C 180 ampere (1000 V) 70 °C 180 ampere (690 V) 40 °C 250 No unit (690 V) 55 °C 230 No unit (690 V) 70 °C 180 No unit |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 145 A (440 V) 55 °C 145 A (500 V) 55 °C 145 A (690 V) 55 °C 120 A (1000 V) 55 °C 80 A (380 / 400 V) 55 °C 145 A (220 / 230 / 240 V) 55 °C 145 |
Rated Operational Power AC-3 (Pe) | (415 V) 75 kW (440 V) 75 kW (500 V) 90 kW (690 V) 110 kW (380 / 400 V) 75 kW (220 / 230 / 240 V) 45 kW |
Rated Operational Voltage | Main Circuit 690 V |