A145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor

ABB
SKU
AB_1SFL471001R8011
Model
A145-30-11-80

Obsolete

Short description of A145 30 11 80

A145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
Obsolete
*All information are subjected to changes without prior notice.
A 3-phase Contactor suitable for various applications such as Motor starting, Isolation, By-pass and Distribution application up to max 1000 V.Operated with control voltage, versions from 24….690 AC, 50 and 60 Hz
MAIN SPECIFICATION
ABB Global IDABB1SFL471001R8011
Business Area (Master Data) NameElectrification
Catalog DescriptionA145-30-11 220-230V 50Hz / 230-240V 60Hz Contactor
Division (Master Data) NameSmart Power
EAN7320500203286
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt
acc. to UL/CSA 600 volt
SKU ID1SFL471001R8011
TECHNICAL
Coil ConsumptionHolding at Max. Rated Control Circuit Voltage 50 Hz 35 V·A
Holding at Max. Rated Control Circuit Voltage 60 Hz 40 V·A
Pull-in at Max. Rated Control Circuit Voltage 50 Hz 550 V·A
Pull-in at Max. Rated Control Circuit Voltage 60 Hz 600 V·A
Coil Operating Limits(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²
Flexible 2x0.75 ... 2.5 mm²
Solid 2 x 1 ... 4 mm²
Stranded 2 x 1 .... 4 mm²
Connecting Capacity Main CircuitBar 24 mm²
Rigid Al-Cable 1 x 25 ... 150 mm²
Rigid Cu-Cable 1 x 6 ... 185 mm²
Connecting Terminals (delivered In Open Position) Main PolesFlat type c/w screws and bolts
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 250 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1500 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 1200 A
Maximum Electrical Switching Frequency(AC-1) 300 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 300 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Mechanical Durability5 million
Operate TimeBetween Coil De-energization and NC Contact Closing 5 ... 10 ms
Between Coil De-energization and NO Contact Opening 9 ... 13 ms
Between Coil Energization and NC Contact Opening 8 ... 22 ms
Between Coil Energization and NO Contact Closing 13 ... 27 ms
Rated Breaking Capacity AC-3 Acc. To IEC 60947-4-18 x Ie AC-3
Rated Frequency (f)Main Circuit 50 / 60 Hz
Rated Making Capacity AC-3 Acc. To IEC 60947-4-110 x Ie AC-3
Rated Operational Current DC-1 (Ie)(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-3 (Ie)(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Operational Current DC-5 (Ie)(110 V) 2 Poles in Series, 40 °C 250 A
(220 V) 3 Poles in Series, 40 °C 250 A
Rated Short-time Withstand Current (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 1200 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 280 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1800 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 800 A
Short-Circuit Protective DevicesgG Type Fuses 315 A
Terminal TypeMain Circuit: Bars
TECHNICAL UL/CSA
General Use Rating UL/CSA(600 V AC) 230 A
Horsepower Rating UL/CSA(200 V AC) Three Phase 40 hp
(208 V AC) Three Phase 40 hp
(220 ... 240 V AC) Three Phase 50 hp
(440 ... 480 V AC) Three Phase 100 hp
(550 ... 600 V AC) Three Phase 125 hp
Maximum Operating Voltage UL/CSAMain Circuit 600 V
ORDERING
Minimum Order Quantity1 piece
ENVIRONMENTAL
Maximum Operating Altitude Permissible3000 m
Resistance To Shock Acc. To IEC 60068-2-27Shock Direction: A 5 K40
Shock Direction: B1 5 K40
Shock Direction: B2 5 K40
Shock Direction: C1 5 K40
Shock Direction: C2 5 K40
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
E-Number (Finland)3709327
E-Number (Norway)4115096
E-Number (Sweden)3227854
EClassV11.0 : 27371003
ETIM 4EC000066 - Magnet contactor, AC-switching
ETIM 5EC000066 - Magnet contactor, AC-switching
ETIM 6EC000066 - Power contactor, AC switching
ETIM 7EC000066 - Power contactor, AC switching
IDEA Granular Category Code (IGCC)4755 >> Contactors
Object Classification CodeQ
UNSPSC39121529
OTHER
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay (0.85 ... 1.1 Uc) -25 ... +50 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +70 °C
Close to Contactor for Storage -40 ... +70 °C
Degree Of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Number Of Auxiliary Contacts NC1
Number Of Auxiliary Contacts NO1
Number Of Main Contacts NO3
Number Of Poles3
Product Net Width111.5
Rated Control Circuit Voltage (Uc)50 Hz 220 ... 230 V
60 Hz 230 ... 240 V
Rated Impulse Withstand Voltage (Uimp)Main Circuit 8 kilovolt
Rated Operational Current AC-1 (Ie)(1000 V) 40 °C 180 ampere
(1000 V) 55 °C 180 ampere
(1000 V) 70 °C 180 ampere
(690 V) 40 °C 250 No unit
(690 V) 55 °C 230 No unit
(690 V) 70 °C 180 No unit
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 145 A
(440 V) 55 °C 145 A
(500 V) 55 °C 145 A
(690 V) 55 °C 120 A
(1000 V) 55 °C 80 A
(380 / 400 V) 55 °C 145 A
(220 / 230 / 240 V) 55 °C 145
Rated Operational Power AC-3 (Pe)(415 V) 75 kW
(440 V) 75 kW
(500 V) 90 kW
(690 V) 110 kW
(380 / 400 V) 75 kW
(220 / 230 / 240 V) 45 kW
Rated Operational VoltageMain Circuit 690 V