OS250D04FP SWITCH FUSE
ABB
SKU
AB_1SCA022726R8620
Model
OS250D04FP
SGD $808.54
Short description of OS250D04FP
OS250D04FP SWITCH FUSE
Country of Origin
Finland (FI)
Switch Fuses,Front Operated,4-pole,04 (Left Side),DIN,0,1,Handle and shaft included,Switched - Fusible Pole
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SCA022726R8620 |
Business Area (Master Data) Name | Electrification |
Catalog Description | OS250D04FP SWITCH FUSE |
Division (Master Data) Name | Smart Power |
EAN | 6417019235141 |
Rated Insulation Voltage (Ui) | 1000 volt |
Rated Operation Current | MainCircuit 250 ampere |
SKU ID | 1SCA022726R8620 |
TECHNICAL | |
Conventional Free-air Thermal Current (Ith) | q = 40 °C 250 A |
Conventional Thermal Current (Ithe) | Fully Enclosed 250 A |
Fourth Pole Type | Switched - Fusible Pole |
Fuse Size | 0,1 |
Fuse System | DIN |
Fuse Type | DIN |
Handle Type | Pistol handle and shaft included |
Operating Mode | Front Operated |
Pollution Degree | 3 |
Position Of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
Power Loss | at Rated Operating Conditions per Pole 23 W |
Rated Operational Current AC-21A (Ie) | (500 V) 250 A (690 V) 250 A |
Rated Short-time Withstand Current (Icw) | for 1 s 8 kiloampere rms |
Standards | IEC 60947-3 |
Switches Operating Mechanism | 04 (Left Side) |
Terminal Type | Lug terminals |
Terminal Width | 25 mm |
Tightening Torque | 30 ... 44 N·m |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
RoHS Status | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
CLASSIFICATIONS | |
ETIM 4 | EC001040 - Fuse switch disconnector |
ETIM 5 | EC001040 - Fuse switch disconnector |
ETIM 6 | EC001040 - Fuse switch disconnector |
ETIM 7 | EC001040 - Fuse switch disconnector |
ETIM 8 | EC001040 - Fuse switch disconnector |
Object Classification Code | Q |
UNSPSC | 39122233 |
OTHER | |
Mounting Type | Base mounting |
Number Of Poles | 4 |
Product Net Width | 262 |
Rated Conditional Short-Circuit Current (Inc) | (690 V) 80 kA |
Rated Impulse Withstand Voltage (Uimp) | 12 kilovolt |
Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A |
Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 250 A (500 V) 250 A (690 V) 250 A |
Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 75 kW (400 V) 140 kW (415 V) 145 kW (500 V) 170 kW (690 V) 250 kW |
Rated Operational Voltage | Main Circuit 690 V AC |
WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |