AF52-30-11-14 250-500V50/60HZ-DC Contactor

ABB
SKU
AB_1SBL367001R1411
Model
AF52-30-11-14
SGD $132.25

Short description of AF52 30 11 14

AF52-30-11-14 250-500V50/60HZ-DC Contactor
Country of Origin
France (FR)
-
+

UOM: Piece

In stock
In Stock 4
Backorder Leadtime: 6 To 8 Weeks

Certificate of Conformance (COC) can be provided upon purchase subjected to manufacturer approval.

*All information are subjected to changes without prior notice.
The AF52-30-11-14 is a 3 pole - 690 V IEC or 600 UL contactor with pre-mounted auxiliary contacts and screw terminals, controlling motors up to 22 kW / 400 V AC (AC-3) or 40 hp / 480 V UL and switching power circuits up to 100 A (AC-1) or 80 A UL general use. Thanks to the AF technology, the contactor has a wide control voltage range (250-500 V 50/60 Hz and DC), managing large control voltage variations, reducing panel energy consumptions and ensuring distinct operations in unstable networks. Furthermore, surge protection is built-in, offering a compact solution. AF contactors have a block type design, can be easily extended with add-on auxiliary contact blocks and an additional wide range of accessories.
MAIN SPECIFICATION
ABB Global IDABB1SBL367001R1411
Business Area (Master Data) NameElectrification
Catalog DescriptionAF52-30-11-14 250-500V50/60HZ-DC Contactor
Division (Master Data) NameSmart Power
EAN3471523132443
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 690 volt
acc. to UL/CSA 600 volt
SKU ID1SBL367001R1411
TECHNICAL
Connecting Capacity Auxiliary CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Control CircuitFlexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 2x 0.75 ... 1.5 mm²
Rigid 1/2x 1 ... 2.5 mm²
Connecting Capacity Main CircuitFlexible with Ferrule 1/2x 4 ... 35 mm²
Flexible with Insulated Ferrule 1/2x 4 ... 35 mm²
Rigid 1/2x 6 ... 3 5 mm²
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 105 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 950 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 600 A
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-15) 1200 cycles per hour
(AC-2 / AC-4) 150 cycles per hour
(AC-3) 1200 cycles per hour
(DC-13) 900 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Operate TimeBetween Coil De-energization and NC Contact Closing 19 ... 105 ms
Between Coil De-energization and NO Contact Opening 17 ... 100 ms
Between Coil Energization and NC Contact Opening 38 ... 95 ms
Between Coil Energization and NO Contact Closing 42 ... 100 ms
Rated Frequency (f)Auxiliary Circuit 50 / 60 Hz
Main Circuit 50 / 60 Hz
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(400 / 440 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 6 A / 144 W
(48 V) 2.8 A / 134 W
(72 V) 1 A / 72 W
(110 V) 0.55 A / 60 W
(125 V) 0.55 A / 69 W
(220 V) 0.27 A / 60 W
(250 V) 0.27 A / 68 W
(400 V) 0.15 A / 60 W
(500 V) 0.13 A / 65 W
(600 V) 0.1 A / 60 W
Rated Short-time Withstand Current (Icw)at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 600 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 110 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 250 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 1000 A
at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 350 A
for 0.1 s 140 A
for 1 s 100 A
Terminal TypeScrew Terminals
Wire Stripping LengthMain Circuit 16 mm
TECHNICAL UL/CSA
General Use Rating UL/CSA(600 V AC) 80 A
Horsepower Rating UL/CSA(120 V AC) Single Phase 3 hp
(200 ... 208 V AC) Three Phase 15 hp
(220 ... 240 V AC) Three Phase 20 hp
(240 V AC) Single Phase 10 hp
(440 ... 480 V AC) Three Phase 40 hp
(550 ... 600 V AC) Three Phase 50 hp
Tightening Torque UL/CSAAuxiliary Circuit 11 IA
Control Circuit 11 IA
Main Circuit 35 IA
ORDERING
Minimum Order Quantity1 piece
ENVIRONMENTAL
Climatic WithstandCategory B according to IEC 60947-1 Annex Q
Maximum Operating Altitude Permissible3000 m
Resistance To Shock Acc. To IEC 60068-2-27Closed, Shock Direction: A 25 K40
Closed, Shock Direction: B1 25 K40
Closed, Shock Direction: B2 15 K40
Closed, Shock Direction: C1 25 K40
Closed, Shock Direction: C2 25 K40
Open, Shock Direction: B1 5 K40
Resistance To Vibrations Acc. To IEC 60068-2-65 ... 300 Hz 3 g closed position / 3 g open position
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
E-Number (Finland)3707024
EClassV11.0 : 27371003
ETIM 4EC000066 - Magnet contactor, AC-switching
ETIM 5EC000066 - Magnet contactor, AC-switching
ETIM 6EC000066 - Power contactor, AC switching
ETIM 7EC000066 - Power contactor, AC switching
Object Classification CodeQ
UNSPSC39121529
OTHER
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... +60 °C
Close to Contactor without Thermal O/L Relay -40 ... +70 °C
Close to Contactor for Storage -60 ... +80 °C
Degree Of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP40
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP10
Number Of Auxiliary Contacts NC1
Number Of Auxiliary Contacts NO1
Number Of Main Contacts NO3
Product Net Width67
Rated Control Circuit Voltage (Uc)50 Hz 250 ... 500 V
50 Hz / 60 Hz 250 ... 500 V
60 Hz 250 ... 500 V
DC Operation 250 ... 500 V
Rated Impulse Withstand Voltage (Uimp)6 kilovolt
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 100 No unit
(690 V) 60 °C 80 ampere
(690 V) 70 °C 70 No unit
Rated Operational Current AC-3 (Ie)(415 V) 60 °C 53 A
(440 V) 60 °C 53 A
(500 V) 60 °C 45 A
(690 V) 60 °C 35 A
(380 / 400 V) 60 °C 53 A
(220 / 230 / 240 V) 60 °C 53 A
Rated Operational Power AC-3 (Pe)(400 V) 22 kW
(415 V) 30 kW
(440 V) 30 kW
(500 V) 30 kW
(690 V) 30 kW
(380 / 400 V) 22 kW
(220 / 230 / 240 V) 15 kW
Rated Operational VoltageAuxiliary Circuit 690 V
Main Circuit 690 V