A30-30-10 110V 50Hz / 110-120V 60Hz Contactor

ABB
SKU
AB_1SBL281001R8410
Model
A30-30-10-110V-50Hz-/-110-120V-60Hz

Obsolete

Short description of A30 30 10 110V 50Hz / 110 120V 60Hz

A30-30-10 110V 50Hz / 110-120V 60Hz Contactor
Obsolete
*All information are subjected to changes without prior notice.
A30 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
MAIN SPECIFICATION
ABB Global IDABB1SBL281001R8410
Business Area (Master Data) NameElectrification
Catalog DescriptionA30-30-10 110V 50Hz / 110-120V 60Hz Contactor
Division (Master Data) NameSmart Power
EAN3471522071842
Rated Insulation Voltage (Ui)acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt
acc. to UL/CSA 600 volt
SKU ID1SBL281001R8410
TECHNICAL
Coil ConsumptionAverage Holding Value 50 / 60 Hz 12 V·A
Average Pull-in Value 50 Hz 125 V·A
Average Pull-in Value 60 Hz 120 V·A
Connecting Capacity Auxiliary CircuitFlexible with Cable End 0.75 ... 2.5 mm²
Rigid Cable 1 ... 4 mm²
Connecting Capacity Main CircuitFlexible with Cable End 2.5 ... 10 mm²
Rigid Cable 2.5 ... 16 mm²
Connecting Terminals (delivered In Open Position) Main PolesM 5 (+,-) pozidriv 2 screw with 2x (5.6x6.5 mm) connector
Conventional Free-air Thermal Current (Ith)acc. to IEC 60947-4-1, Open Contactors q = 40 °C 65 A
acc. to IEC 60947-5-1, q = 40 °C 16 A
Maximum Breaking Capacitycos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 820 A
cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 340 A
Maximum Electrical Switching Frequency(AC-1) 600 cycles per hour
(AC-2 / AC-4) 300 cycles per hour
(AC-3) 1200 cycles per hour
Maximum Mechanical Switching Frequency3600 cycles per hour
Operate TimeBetween Coil De-energization and NO Contact Opening 4 ... 11 ms
Between Coil Energization and NO Contact Closing 8 ... 21 ms
Rated Breaking Capacity AC-3 Acc. To IEC 60947-4-18 x Ie AC-3
Rated Frequency (f)Supply Circuit 50 / 60 Hz
Rated Making Capacity AC-3 Acc. To IEC 60947-4-110 x Ie AC-3
Rated Operational Current AC-15 (Ie)(500 V) 2 A
(690 V) 2 A
(24 / 127 V) 6 A
(220 / 240 V) 4 A
(380 / 400 V) 3 A
Rated Operational Current DC-13 (Ie)(24 V) 6 / 144 A
(48 V) 2.8 / 134 A
(72 V) 2 / 144 A
(125 V) 1.1 / 138 A
(250 V) 0.55 / 138 A
Short-Circuit Protective DevicesAuxiliary Circuit - gG Type Fuses 10 A
gG Type Fuses 63 A
StandardsDevices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1
Terminal TypeScrew Terminals
ORDERING
Minimum Order Quantity1 piece
ENVIRONMENTAL
Climatic Withstandacc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II
Maximum Operating Altitude Permissible3000 m
Resistance To Shock Acc. To IEC 60068-2-27Closed, Shock Direction: B1 10 K40
Open, Shock Direction: B1 5 K40
Shock Direction: A 20 K40
Shock Direction: B2 15 K40
Shock Direction: C1 20 K40
Shock Direction: C2 20 K40
RoHS StatusFollowing EU Directive 2011/65/EU
CLASSIFICATIONS
E-Number (Finland)3709143
EClassV11.0 : 27371003
ETIM 4EC000066 - Magnet contactor, AC-switching
ETIM 5EC000066 - Magnet contactor, AC-switching
ETIM 6EC000066 - Power contactor, AC switching
ETIM 7EC000066 - Power contactor, AC switching
Object Classification CodeQ
UNSPSC39121529
OTHER
Ambient Air TemperatureClose to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C
Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C
Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C
Close to Contactor for Storage -60 ... +80 °C
Degree Of Protectionacc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20
Number Of Auxiliary Contacts NO1
Number Of Main Contacts NO3
Product Net Width54
Rated Control Circuit Voltage (Uc)50 Hz 110 V
60 Hz 110 ... 120 V
Rated Impulse Withstand Voltage (Uimp)8 kilovolt
Rated Operational Current AC-1 (Ie)(690 V) 40 °C 55 No unit
(690 V) 55 °C 55 No unit
(690 V) 70 °C 39 No unit
Rated Operational Current AC-3 (Ie)(415 V) 55 °C 32 A
(440 V) 55 °C 32 A
(500 V) 55 °C 28 A
(690 V) 55 °C 21 A
(380 / 400 V) 55 °C 32 A
(220 / 230 / 240 V) 55 °C 33
Rated Operational Power AC-3 (Pe)(415 V) 15 kW
(440 V) 18.5 kW
(500 V) 18.5 kW
(690 V) 18.5 kW
(380 / 400 V) 15 kW
(220 / 230 / 240 V) 9 kW
Rated Operational Power AC-6b (Pe)(230 / 240 V) 40 °C, 50 / 60 Hz 13 kvar
(230 / 240 V) 55 °C, 50 / 60 Hz 13 kvar
(230 / 240 V) 70 °C, 50 / 60 Hz 11 kvar
(400 / 415 V) 40 °C, 50 / 60 Hz 22 kvar
(400 / 415 V) 70 °C, 50 / 60 Hz 18.5 kvar
(400 / 415 V) 55 °C, 50 / 60 Hz 22 kvar
(440 V) 40 °C, 50 / 60 Hz 24 kvar
(440 V) 55 °C, 50 / 60 Hz 24 kvar
(440 V) 70 °C, 50 / 60 Hz 20.5 kvar
(500 / 550 V), 40 °C, 50 / 60 Hz 28 kvar
(500 / 550 V) 55 °C, 50 / 60 Hz 28 kvar
(500 / 550 V) 70 °C, 50 / 60 Hz 23 kvar
(690 V) 40 °C, 50 / 60 Hz 38 kvar
(690 V) 55 °C, 50 / 60 Hz 38 kvar
(690 V) 70 °C, 50 / 60 Hz 32 kvar
Rated Operational VoltageMain Circuit 690 V