A26-30-10 380-400V 50Hz / 400-415V 60Hz Contactor
ABB
SKU
AB_1SBL241001R8510
Model
A26-30-10-380-400V-50Hz-/-400-415V-60Hz
SGD $72.42
Short description of A26 30 10 380 400V 50Hz / 400 415V 60Hz
A26-30-10 380-400V 50Hz / 400-415V 60Hz Contactor
Country of Origin
Bulgaria (BG)
A26 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SBL241001R8510 |
Business Area (Master Data) Name | Electrification |
Catalog Description | A26-30-10 380-400V 50Hz / 400-415V 60Hz Contactor |
Division (Master Data) Name | Smart Power |
EAN | 3471522062857 |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt acc. to UL/CSA 600 volt |
SKU ID | 1SBL241001R8510 |
TECHNICAL | |
Coil Consumption | Average Holding Value 50 / 60 Hz 12 V·A Average Pull-in Value 50 Hz 125 V·A Average Pull-in Value 60 Hz 120 V·A |
Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² |
Connecting Capacity Main Circuit | Flexible with Cable End 0.75 ... 4 mm² Rigid Cable 1.5 ... 6 mm² |
Connecting Terminals (delivered In Open Position) Main Poles | M 4 (+,-) pozidriv 2 screws with cable clamp |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 45 A acc. to IEC 60947-5-1, q = 40 °C 16 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 170 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-2 / AC-4) 300 cycles per hour (AC-3) 1200 cycles per hour |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Mechanical Durability | 10 million |
Operate Time | Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 8 ... 21 ms |
Rated Breaking Capacity AC-3 Acc. To IEC 60947-4-1 | 8 x Ie AC-3 |
Rated Frequency (f) | Supply Circuit 50 / 60 Hz |
Rated Making Capacity AC-3 Acc. To IEC 60947-4-1 | 10 x Ie AC-3 |
Rated Operational Current AC-15 (Ie) | (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A |
Rated Operational Current DC-13 (Ie) | (24 V) 6 / 144 A (48 V) 2.8 / 134 A (72 V) 2 / 144 A (125 V) 1.1 / 138 A (250 V) 0.55 / 138 A |
Short-Circuit Protective Devices | Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 50 A |
Terminal Type | Screw Terminals |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | 3000 m |
Resistance To Shock Acc. To IEC 60068-2-27 | Closed, Shock Direction: B1 10 K40 Open, Shock Direction: B1 5 K40 Shock Direction: A 20 K40 Shock Direction: B2 15 K40 Shock Direction: C1 20 K40 Shock Direction: C2 20 K40 |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
EClass | V11.0 : 27371003 |
ETIM 4 | EC000066 - Magnet contactor, AC-switching |
ETIM 5 | EC000066 - Magnet contactor, AC-switching |
ETIM 6 | EC000066 - Power contactor, AC switching |
ETIM 7 | EC000066 - Power contactor, AC switching |
Object Classification Code | Q |
UNSPSC | 39121529 |
OTHER | |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C |
Degree Of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Number Of Auxiliary Contacts NO | 1 |
Number Of Main Contacts NO | 3 |
Product Net Width | 54 |
Rated Control Circuit Voltage (Uc) | 50 Hz 380 ... 400 V 60 Hz 400 ... 415 V |
Rated Impulse Withstand Voltage (Uimp) | 8 kilovolt |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 45 No unit (690 V) 55 °C 40 No unit (690 V) 70 °C 32 No unit |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 26 A (440 V) 55 °C 26 A (500 V) 55 °C 22 A (690 V) 55 °C 17 A (380 / 400 V) 55 °C 26 A (220 / 230 / 240 V) 55 °C 26 |
Rated Operational Power AC-3 (Pe) | (415 V) 11 kW (440 V) 15 kW (500 V) 15 kW (690 V) 15 kW (380 / 400 V) 11 kW (220 / 230 / 240 V) 6.5 kW |
Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 11.5 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 11.5 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 9 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 19 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 15 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 19 kvar (440 V) 40 °C, 50 / 60 Hz 20 kvar (440 V) 55 °C, 50 / 60 Hz 20 kvar (440 V) 70 °C, 50 / 60 Hz 16.5 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 23 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 23 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 19 kvar (690 V) 40 °C, 50 / 60 Hz 32 kvar (690 V) 55 °C, 50 / 60 Hz 32 kvar (690 V) 70 °C, 50 / 60 Hz 26 kvar |
Rated Operational Voltage | Main Circuit 690 V |