Circuit breaker, ComPacT NSX250H, 70kA/415VAC, 3 poles, MicroLogic 2.2M trip unit 220A
Schneider
SKU
SE_C25H32M220
Model
C25H32M220
SGD $1,190.47 All prices inclusive of GST
Short description of C25H32M220
This ComPacT NSX250H is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic MicroLogic 2.2 M trip unit, with 220A rating. MicroLogic 2.2 M trip unit provides adjustable long time and short time protections, and fixed instantaneous protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX250H is part of Schneider Electric EcoStruxure Power architecture.
Country of Origin
China
Schneider Electric green signature style for the entire ComPacT range
Estimated 40% reduction of wiring time for panel builders
Experience easier installation thanks to a new ergonomic front-plate design
Gain the confidence that all auxiliaries are on the right spot, and check that you have the right coil rating
Ergonomic new toggle for easier breaker manual operation
MAIN | |
---|---|
Range | ComPacT new generation |
Product Name | ComPacT NSX new generation |
Device Short Name | NSX250H |
Product Or Component Type | Circuit breaker |
Device Application | Motor protection |
Poles Description | 3P |
Protected Poles Description | 3D |
[In] Rated Current | 220 A at 65 °C |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
Network Type | AC |
Network Frequency | 50/60 Hz |
Suitability For Isolation | Yes conforming to EN/IEC 60947-2 |
Utilisation Category | Category A |
[Icu] Rated Ultimate Short-circuit Breaking Capacity | 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 600 V AC 50/60 Hz conforming to UL 508 |
Performance Level | H 70 kA 415 V AC |
Trip Unit Name | MicroLogic 2.2 M |
Trip Unit Technology | Electronic |
Trip Unit Protection Functions | LSoI |
Control Type | Toggle |
Circuit Breaker Mounting Mode | Fixed |
COMPLEMENTARY | |
[Ui] Rated Insulation Voltage | 800 V AC 50/60 Hz |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
[Ics] Rated Service Short-circuit Breaking Capacity | 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical Durability | 20000 cycles |
Electrical Durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
Power Dissipation Per Pole | 13.55 W |
Mounting Support | Backplate |
Mounting Position | Horizontal and vertical Flat on the back |
Upside Connection | Front |
Downside Connection | Front |
Connection Pitch | 35 mm |
Protection Type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection |
Trip Unit Rating | 220 A at 65 °C |
Motor Tripping Class | 20 5 10 |
Complementary Motor Protection | Phase unbalance |
Long-time Pick-up Adjustment Type Ir (thermal Protection) | Adjustable 9 settings |
[Ir] Long-time Protection Pick-up Adjustment Range | 100...220 A |
Long-time Protection Delay Adjustment Type Tr | Fixed |
[tr] Long-time Protection Delay Adjustment Range | 120 s at 1.5 x Ir for trip class 5 6.5 s at 6 x Ir for trip class 5 5 s at 7.2 x Ir for trip class 5 240 s at 1.5 x Ir for trip class 10 13.5 s at 6 x Ir for trip class 10 10 s at 7.2 x Ir for trip class 10 480 s at 1.5 x Ir for trip class 20 26 s at 6 x Ir for trip class 20 20 s at 7.2 x Ir for trip class 20 |
Thermal Memory | 20 minutes before and after tripping |
Short-time Protection Pick-up Adjustment Type Isd | Adjustable 9 settings |
[Isd] Short-time Protection Pick-up Adjustment Range | 5...13 x Ir |
Short-time Protection Delay Adjustment Type Tsd | Fixed |
Instantaneous Protection Pick-up Adjustment Type Ii | Fixed |
[Ii] Instantaneous Protection Pick-up Adjustment Range | 3300 A |
Earth-leakage Protection | Without |
Zone Selective Interlocking ZSI | Without |
Number Of Slots For Electrical Auxiliaries | 5 slot(s) |
Local Signalling | Flashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point |
Width (W) | 105 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
Net Weight | 2.4 kg |
ENVIRONMENT | |
Standards | EN/IEC 60947 |
Product Certifications | CCC EAC Marine |
Overvoltage Category | Class II |
Electrical Shock Protection Class | Class II |
Pollution Degree | 3 conforming to IEC 60664-1 |
IP Degree Of Protection | IP40 conforming to IEC 60529 |
IK Degree Of Protection | IK07 conforming to IEC 62262 |
Ambient Air Temperature For Operation | -25…70 °C |
Ambient Air Temperature For Storage | -50…85 °C |
Relative Humidity | 0…95 % |
Operating Altitude | 0...2000 m without derating 2000 m...5000 m with derating |