trip unit MicroLogic 6.2 E for ComPacT NSX 160/250 circuit breakers, electronic, rating 160A, 3 poles 3d
Schneider
SKU
SE_C1636E160
Model
C1636E160
SGD $1,697.38 All prices inclusive of GST
Short description of C1636E160
This MicroLogic 6.2 E (Energy) is a 3 poles 3d electronic trip unit used on ComPacT NSX 160/250 circuit breakers. This 160A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. It has an additional and adjustable ground fault protection. MicroLogic 6.2 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. MicroLogic 6.2 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and ComPacT NSX basic frame.
Country of Origin
China
MAIN | |
---|---|
Range | ComPacT new generation |
Range Of Product | ComPacT NSX100...250 new generation |
Product Or Component Type | Trip unit |
Trip Unit Name | MicroLogic 6.2 E |
Trip Unit Technology | Electronic |
Range Compatibility | ComPacT new generation NSX160 ComPacT new generation NSX250 |
Device Application | Distribution |
Poles Description | 3P |
Protected Poles Description | 3D |
Trip Unit Protection Functions | LSIG |
Protection Type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection |
Trip Unit Rating | 160 A at 40 °C |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
Network Type | AC |
Network Frequency | 50/60 Hz |
Circuit Breaker Mounting Mode | Fixed |
COMPLEMENTARY | |
Long-time Pick-up Adjustment Type Ir (thermal Protection) | Adjustable 9 settings |
[Ir] Long-time Protection Pick-up Adjustment Range | 63...160 A |
Long-time Protection Delay Adjustment Type Tr | Adjustable |
[tr] Long-time Protection Delay Adjustment Range | 15…400 s at 1.5 x Ir 0.35…11 s at 7.2 x Ir 0.5…16 s at 6 x Ir |
Thermal Memory | 20 minutes before and after tripping |
Short-time Protection Pick-up Adjustment Type Isd | Adjustable 9 settings |
[Isd] Short-time Protection Pick-up Adjustment Range | 1.5...10 x Ir |
Short-time Protection Delay Adjustment Type Tsd | Adjustable |
[tsd] Short-time Protection Delay Adjustment Range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
Instantaneous Protection Pick-up Adjustment Type Ii | Adjustable |
[Ii] Instantaneous Protection Pick-up Adjustment Range | 1.5...15 x In |
Ground-fault Protection Pick-up Adjustment Type Ig | Adjustable |
[Ig] Ground-fault Protection Pick-up Adjustment Range | 0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off |
Ground-fault Protection Time Delay Adjustment Type Tg | Adjustable |
[tg] Ground-fault Protection Time Delay Adjustment Range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
Earth-leakage Protection | Without |
Zone Selective Interlocking ZSI | With |
Local Signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
Display Type | LCD display |
Type Of Measurement | Energy meter |
Communication Of Data | Energy metering Protection and alarm settings Time-stamped histories and event tables Instantaneous and demand values Maintenance indicators Demand current and power Power quality Maximeters/minimeters |
Electrical Data Recording | Maintenance indicators |
ENVIRONMENT | |
Standards | EN/IEC 60947-2 |
Electrical Shock Protection Class | Class II |
Pollution Degree | 3 conforming to IEC 60947-1 |
IP Degree Of Protection | IP40 conforming to IEC 60529 |
Ambient Air Temperature For Operation | -25…70 °C |
Ambient Air Temperature For Storage | -40…85 °C |
Write Your Own Review