circuit breaker ComPacT NSX100R, 200 kA at 415 VAC, MicroLogic 6.2 E trip unit 40 A, 4 poles 4d
Schneider
SKU
SE_C10R46E040
Model
C10R46E040
SGD $2,464.20 All prices inclusive of GST
Short description of C10R46E040
This ComPacT NSX100R is a complete 4P 4d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 200kA rms at 415VAC 50/60Hz and 45kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 40A rating electronic MicroLogic 6.2 E trip unit, with an adjustable ground-fault protection (with OFF position). MicroLogic 6.2 E trip unit provides adjustable long time, short time and instantaneous protection. MicroLogic 6.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 4 poles version (140mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. ComPacT NSX100R is part of Schneider Electric EcoStruxure Power architecture.
Country of Origin
Poland
MAIN | |
---|---|
Range | ComPacT new generation |
Product Name | ComPacT NSX new generation |
Device Short Name | NSX100R |
Product Or Component Type | Circuit breaker |
Device Application | Distribution |
Poles Description | 4P |
Protected Poles Description | 4D 3D + OSN 3D + N/2 3D |
Neutral Position | Left |
[In] Rated Current | 40 A at 40 °C |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
Network Type | AC |
Network Frequency | 50/60 Hz |
Suitability For Isolation | Yes conforming to EN/IEC 60947-2 |
Utilisation Category | Category A |
[Icu] Rated Ultimate Short-circuit Breaking Capacity | 200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Performance Level | R 200 kA 415 V AC |
Trip Unit Name | MicroLogic 6.2 E |
Trip Unit Technology | Electronic |
Trip Unit Protection Functions | LSIG |
Control Type | Toggle |
Circuit Breaker Mounting Mode | Fixed |
COMPLEMENTARY | |
[Ui] Rated Insulation Voltage | 800 V AC 50/60 Hz |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
[Ics] Rated Service Short-circuit Breaking Capacity | 200 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
Mechanical Durability | 20000 cycles |
Electrical Durability | 20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In |
Power Dissipation Per Pole | 1.34 W |
Mounting Support | Backplate |
Mounting Position | Horizontal and vertical Flat on the back |
Upside Connection | Front |
Downside Connection | Front |
Connection Pitch | 35 mm |
Protection Type | L : for overload protection (long time) S : for short time short-circuit protection I : for instantaneous short-circuit protection G : for ground fault protection |
Trip Unit Rating | 40 A at 40 °C |
Long-time Pick-up Adjustment Type Ir (thermal Protection) | Adjustable 9 settings |
[Ir] Long-time Protection Pick-up Adjustment Range | 18...40 A |
Long-time Protection Delay Adjustment Type Tr | Adjustable |
[tr] Long-time Protection Delay Adjustment Range | 15…400 s at 1.5 x Ir 0.5…16 s at 6 x Ir 0.35…11 s at 7.2 x Ir |
Neutral Protection Settings | 0.5 x Ir (3D + N/2) 1 x Ir (4D) 1.6 x Ir (3D + OSN) No protection (3D) |
Thermal Memory | 20 minutes before and after tripping |
Short-time Protection Pick-up Adjustment Type Isd | Adjustable |
[Isd] Short-time Protection Pick-up Adjustment Range | 1.5...10 x Ir |
Short-time Protection Delay Adjustment Type Tsd | Adjustable |
[tsd] Short-time Protection Delay Adjustment Range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
Instantaneous Protection Pick-up Adjustment Type Ii | Adjustable |
[Ii] Instantaneous Protection Pick-up Adjustment Range | 1.5...15 x In |
Ground-fault Protection Pick-up Adjustment Type Ig | Adjustable 9 settings |
[Ig] Ground-fault Protection Pick-up Adjustment Range | 0.4...1 x In for In = 40 A 0.2...1 x In for In > 40 A Ig enable on/off |
Ground-fault Protection Time Delay Adjustment Type Tg | Adjustable 5 settings |
[tg] Ground-fault Protection Time Delay Adjustment Range | 0…0.4 s I²t=off 0.1…0.4 s I²t=on |
Earth-leakage Protection | Without |
Zone Selective Interlocking ZSI | With |
Number Of Slots For Electrical Auxiliaries | 5 slot(s) |
Local Signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload |
Display Type | LCD display |
Type Of Measurement | Energy meter |
Communication Of Data | Instantaneous and demand values Time-stamped histories and event tables Energy metering Power quality Demand current and power Protection and alarm settings Maintenance indicators Maximeters/minimeters |
Width (W) | 140 mm |
Height (H) | 161 mm |
Depth (D) | 86 mm |
Net Weight | 2.4 kg |
ENVIRONMENT | |
Standards | EN/IEC 60947 |
Product Certifications | EAC CCC Marine |
Overvoltage Category | Class II |
Electrical Shock Protection Class | Class II |
Pollution Degree | 3 conforming to IEC 60664-1 |
IP Degree Of Protection | IP40 conforming to IEC 60529 |
IK Degree Of Protection | IK07 conforming to IEC 62262 |
Ambient Air Temperature For Operation | -25…70 °C |
Ambient Air Temperature For Storage | -40…85 °C |
Relative Humidity | 0…95 % |
Operating Altitude | 0...2000 m without derating 2000 m...5000 m with derating |