A75-30-00 220-230V 50Hz / 230-240V 60Hz Contactor
ABB
SKU
AB_1SBL411001R8000
Model
A75-30-00-220-230V-50Hz-/-230-240V-60Hz
Obsolete
Short description of A75 30 00 220 230V 50Hz / 230 240V 60Hz
A75-30-00 220-230V 50Hz / 230-240V 60Hz Contactor
Obsolete
A75 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC / 1000 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, front and side-mounted add-on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available.
MAIN SPECIFICATION | |
---|---|
ABB Global ID | ABB1SBL411001R8000 |
Business Area (Master Data) Name | Electrification |
Catalog Description | A75-30-00 220-230V 50Hz / 230-240V 60Hz Contactor |
Division (Master Data) Name | Smart Power |
EAN | 3471522092809 |
Rated Insulation Voltage (Ui) | acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 volt acc. to UL/CSA 600 volt |
SKU ID | 1SBL411001R8000 |
TECHNICAL | |
Coil Consumption | Average Holding Value 50 / 60 Hz 18 V·A Average Pull-in Value 50 Hz 190 V·A Average Pull-in Value 60 Hz 180 V·A |
Connecting Capacity Auxiliary Circuit | Flexible with Cable End 0.75 ... 2.5 mm² Rigid Cable 1 ... 4 mm² |
Connecting Capacity Main Circuit | Flexible with Cable End 6 ... 16 mm² Rigid Cable 6 ... 25 mm² |
Connecting Terminals (delivered In Open Position) Main Poles | M 6 (+,-) pozidriv 2 screws with 1x (13 x 10 mm) connector |
Conventional Free-air Thermal Current (Ith) | acc. to IEC 60947-4-1, Open Contactors q = 40 °C 125 A |
Maximum Breaking Capacity | cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 1300 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 630 A |
Maximum Electrical Switching Frequency | (AC-1) 600 cycles per hour (AC-2 / AC-4) 150 cycles per hour (AC-3) 600 cycles per hour |
Maximum Mechanical Switching Frequency | 3600 cycles per hour |
Mechanical Durability | 10 million |
Operate Time | Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 8 ... 27 ms |
Rated Breaking Capacity AC-3 Acc. To IEC 60947-4-1 | 8 x Ie AC-3 |
Rated Making Capacity AC-3 Acc. To IEC 60947-4-1 | 10 x Ie AC-3 |
Short-Circuit Protective Devices | gG Type Fuses 160 A |
Standards | Devices complying with international standards IEC 947-1 / 947-4-1, and European standards EN 60 947-1 / 60 947-4-1. Electromagnetic compatibility (EMC) acc. to amendment A11 to IEC 947-1, EN 60 947-1 and amendment 2 to IEC 947-4-1 |
Terminal Type | Screw Terminals |
ORDERING | |
Minimum Order Quantity | 1 piece |
ENVIRONMENTAL | |
Climatic Withstand | acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II |
Maximum Operating Altitude Permissible | 3000 m |
Resistance To Shock Acc. To IEC 60068-2-27 | Closed, Shock Direction: B1 10 K40 Open, Shock Direction: B1 5 K40 Shock Direction: A 20 K40 Shock Direction: B2 15 K40 Shock Direction: C1 20 K40 Shock Direction: C2 20 K40 |
RoHS Status | Following EU Directive 2011/65/EU |
CLASSIFICATIONS | |
E-Number (Finland) | 3709224 |
EClass | V11.0 : 27371003 |
ETIM 4 | EC000066 - Magnet contactor, AC-switching |
ETIM 5 | EC000066 - Magnet contactor, AC-switching |
ETIM 6 | EC000066 - Power contactor, AC switching |
ETIM 7 | EC000066 - Power contactor, AC switching |
Object Classification Code | Q |
UNSPSC | 39121529 |
OTHER | |
Ambient Air Temperature | Close to Contactor Fitted with Thermal O/L Relay -25 ... +55 °C Close to Contactor without Thermal O/L Relay (0.85 ... 1.1 Uc) -40 ... +55 °C Close to Contactor without Thermal O/L Relay (Uc) -40 ... +70 °C Close to Contactor for Storage -60 ... +80 °C |
Degree Of Protection | acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 |
Number Of Main Contacts NO | 3 |
Product Net Width | 70 |
Rated Control Circuit Voltage (Uc) | 50 Hz 220 ... 230 V 60 Hz 230 ... 240 V |
Rated Impulse Withstand Voltage (Uimp) | 8 kilovolt |
Rated Operational Current AC-1 (Ie) | (690 V) 40 °C 125 No unit (690 V) 55 °C 105 No unit (690 V) 70 °C 85 No unit |
Rated Operational Current AC-3 (Ie) | (415 V) 55 °C 72 A (440 V) 55 °C 70 A (500 V) 55 °C 65 A (690 V) 55 °C 46 A (1000 V) 55 °C 28 A (380 / 400 V) 55 °C 75 A (220 / 230 / 240 V) 55 °C 75 |
Rated Operational Power AC-3 (Pe) | (415 V) 40 kW (440 V) 40 kW (500 V) 45 kW (690 V) 40 kW (380 / 400 V) 37 kW (220 / 230 / 240 V) 22 kW |
Rated Operational Power AC-6b (Pe) | (230 / 240 V) 40 °C, 50 / 60 Hz 28 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 28 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 24.5 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 48 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 41 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 48 kvar (440 V) 40 °C, 50 / 60 Hz 52 kvar (440 V) 55 °C, 50 / 60 Hz 52 kvar (440 V) 70 °C, 50 / 60 Hz 45 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 60 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 60 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 51 kvar (690 V) 40 °C, 50 / 60 Hz 82 kvar (690 V) 55 °C, 50 / 60 Hz 82 kvar (690 V) 70 °C, 50 / 60 Hz 70 kvar |
Rated Operational Voltage | Main Circuit 1000 V |